8MX28B
4.2 Power Output Capacity
The power plant has two basic configurations:
The first supplies a maximum of 200 amps or 150 amps with N+1 redundancy. The housing
for this configuration provides space for one rectifier shelf that can hold up to four rectifiers,
a control unit, and one tier of up to 24 distribution circuit breakers.
The second supplies a maximum of 400 amps or 350 amps with N+1 redundancy. The
housing for this configuration provides space for two rectifier shelves that can hold up to
four rectifiers each, a control unit, and one tier of up to 24 distribution circuit breakers.
The difference between the 200 and 400 amp units are the side plates and an additional
rectifier shelf; all other parts are the same for both configurations.
4.3 Rectifiers
The rectifiers are Advance Power, Inc. Model MRF28H54BV with specifications as follows:
Input Voltage: 176-264V ac (230V ac nominal) @ 45-66 Hz
Input Current per Rectifier: 13.9 Amps @ 230V ac
Apparent Power Factor: 99% Typical, 98% Minimum
Output Voltage: 54.5V dc
Overvoltage Protection: Set at 59.5V dc
Output Current per Rectifier: 50 Amps Minimum Continuous
Power Output per Rectifier: 2800W Continuous, Vin > 198V ac
Efficiency: 91% Typical
Cooling: Fan cooled, front to rear airflow
Ambient Temperature: -25°C to 65°C Operational
4.4 Control Unit
The microprocessor-based power system control unit is 1U high (1.75”) and provides
control and monitoring functions. Features implemented are:
32-character alphanumeric display
LED alarm and status indicators
Standard voltage and battery charging control
Battery temperature compensation (optional)
Monitoring of up to two shelves of four rectifiers each
Individual alarm monitoring of 24 breakers
Eight alarm / annunciation relays (Major, Minor, and six user defined) with form C
contact outputs
Four external alarm inputs (either N.O. or N.C. contacts)