MX28B 17
30 A FFA-0019
*-1: adapter has #10 studs on 5/8” centers for two-hole cable lug
-2: adapter has #10 studs on ¾” centers for two-hole cable lug
-3: adapter has ¼” studs on 1” centers for two-hole cable lug
Table 5.7-1. Plug-in Circuit Breakers
A list of GMT type fuses available from Advance Power, Inc. is provided in Table 5.7-2.
FUSE RATING PART NUMBER
1/4 A FFA-0030
1/2 A FFA-0031
3/4 A FFA-0032
1 A FFA-0033
1¼ A FFA-0039
1½ A FFA-0035
3 A FFA-0036
5 A FFA-0037
10 A FFA-0038
Table 5.7-2. GMT Fuses
5.7.2 Installation of Circuit Breakers and Fuses
5.7.2.1 Plug-in Circuit Breakers
1) Remove the circuit breaker cover panel and the plastic cover(s) from the desired
location(s).
2) Install the circuit breaker(s) by snapping the top terminal onto the upper bus bar
and rotating the unit down until the second terminal snaps onto the breaker
termination post as shown in Figure 5.7-1. The breaker alarm terminals are
designed to make contact with the alarm terminal board as the breaker is snapped
into place.