American Power Conversion PDU manual Specifications

Models: PDU

1 8
Download 8 pages 44.77 Kb
Page 6
Image 6
Specifications

Installation and Configuration

Global Panel Config. Configures the same number of poles or circuit breaker ratings for all circuit breakers in both distribution panels simultaneously. For example, if your system uses only three-pole, 20-amp circuit breakers, choose this option, scroll to the value 3 for Poles and 020 for Amp Rating. Select Apply Now and YES to implement your changes.

Specifications

Branch Monitor Parameters

Maximum current (RMS): 95A

 

Maximum current (peak): 135A

 

Maximum crest factor: 3

 

Minimum current: 0.5A

 

Measurement accuracy: +/- 0.5A or 5% of reading

 

(whichever is greater)

 

Maximum wire size: 0.35in (8.89mm) maximum diameter

 

 

InfraStruXure System Parameters

Branch circuit range: 20–60A

 

Maximum scan (refresh) time: 3 seconds

 

Display resolution: 0.1A

 

 

6

Branch Current Monitoring Kit

Page 6
Image 6
American Power Conversion PDU manual Specifications