American Power Conversion RT-UXICH user manual High Bypass Point

Models: RT-UXI RT-UXICH

1 20
Download 20 pages 56.39 Kb
Page 12
Image 12
High Bypass Point

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

 

output voltage

+20%

will pass to connected

 

setting

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Low Bypass Point

-30% of output

-15%, -20%, -25%, -30%

Minimum voltage that the UPS

 

voltage setting

 

will pass to connected

 

 

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Output Voltage

230 VAC

220, 225, 230, 240 VAC

Allows the user to select the

 

 

 

output voltage.

 

 

 

 

Output Frequency

Automatic

Automatic

Sets the allowable UPS output

 

50 ± 3 Hz or

50 ± 3 Hz,

frequency. Whenever possible,

 

50 ± 0.1 Hz

the output frequency tracks the

 

60 ± 3 Hz

 

60 ± 3 Hz

input frequency.

 

 

 

 

60 ± 0.1 Hz

 

 

 

 

 

Number of Batteries

1

Number of Connected

Defines the number of

 

 

Batteries

connected batteries for proper

 

 

 

run time prediction.

 

 

 

Default setting of 1 = 1920 VAh

 

 

 

(192 V x 10 Ah)

 

 

 

Setting of 2 = 3840 VAh, etc.

 

 

 

 

10

Page 12
Image 12
American Power Conversion RT-UXICH user manual High Bypass Point