•Wiring must be performed by a qualified electrician.

ATTACH THE BEZEL TO THE UPS

5000/6000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS

Wiring must be performed by a qualified electrician.

Adhere to all national and local electrical codes.

Install a high magnetic 30/32 A utility circuit breaker

Use #10 AWG gauge (5sq. mm) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5sq. mm) wire through the access panel, and connect the wires to the terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not included).