CHAPTER 4: SPECIFICATIONS
Product Specifications
Electrical Specifications
| AP9621 / SUTF3 / SYTF2 / | SYTF2J / SYTF3J / SURT006 |
| SYTF3 / SURT005 |
|
|
|
|
Nominal Input Voltage (VAC) | 208 | 200 |
Input Voltage Range (VAC) | 185 to 230* | 180 to 220 |
|
|
|
Maximum Input Current (amps) |
|
|
Line cord Installation | 24 | 22 |
Hardwire Installation | 26** |
|
Line Frequency (Hz) | 60 | 50 or 60 |
Efficiency | 90 to 95% |
|
Nominal Output Voltage (VAC) | 120 | 100 |
|
|
|
Maximum Output Power (VA) |
|
|
Line cord Installation | 4500* | 3500 |
Hardwire Installation | 5000* | 3500 |
|
|
|
*For continuous operation below Vin = 205 VAC, the output load must be reduced to limit the maximum input current to the amount specified in the table above. Continuous operation above the maximum specified input current may cause the unit to overheat and shutdown. Please contact APC for additional information.
** Not available on SUTF3 and SYTF3 models.
12