Magnum VS 100 Power System
Output Voltage (factory programmed)
Operating Voltage Range
Rated Output Current
Efficiency
Over Voltage Protection
Output Current
Current Limit
Power Output per Rectifier @ 54.5 Vdc
54.0 Vdc
47 – 56.5 Vdc
100 A
85% Typical
59.5 Vdc
90 A Minimum Continuous at 115 Vac Input
105 A Minimum Continuous at 230 Vac Input.
93 A Maximum at 115 Vac Input
110 A Maximum at 230 Vac Input.
4900 W Continuous at 115 Vac Input
5700 W Continuous at 230 Vac Input
8.3.Controls and Indicators
TWF0500H54B Rectifier
Input Healthy LED
Output Healthy LED
Current Limit LED
Overvolts LED
AC power present.
DC output voltage between 39.5 to 59.5 Vdc.
On when rectifier is in current limit.
On when rectifier is above 57 Vdc. (Must be powered down to reset)
Magnum VS Controller
DC OK (Green)
Major (Red)
Minor (Yellow)
Out Relay 1 (Red)
(Flashing Green)
On when voltage is between 50 and 57 Vdc.
On when Major Relay is
On when Minor Relay is energized
On when Output Relay 1 is energized
Watchdog LED
*Major relay is energized in normal operation. If all power fails, major relay will lose power and the contacts will change state, signifying an alarm.
Magnum VS | Page 50 |