2.3.AC Power Connections

WARNING: Ensure that all of the external dc and ac circuit breakers are in the OFF position prior to connecting service to the power plant. Confirm that all voltages have been removed

including any battery sources before proceeding.

AC Connections

The Magnum VS DC power system, specifically each rectifier, requires a single phase input AC supply (Range: 85–264 VAC, 47–63 Hz) to operate. Each Magnum VS shelf has three (3) sets of input terminals (TRM 2, 5, 8; TRM 3, 6, 9; and TRM 4, 7, 10). As a result, each Magnum VS shelf can be wired such that three (3) different AC sources (e.g., three phase, delta or star, connections) provide power to the rectifiers (see Figure 3.3-2), or, a single AC source is used to provide power to the rectifiers, and jumper cables are used to interconnect the different input terminals (as appropriate, and provided the input wiring is not overloaded; see Figure 3.3-1).

The Magnum VS 50 SKUs are shipped configured (including the appropriate jumper cables) for operation from a single AC source.

The Magnum VS 100 SKUs are shipped configured (including the appropriate jumper cables) for operation from two AC sources (one for each shelf).

Figure 2.3-1 Magnum VS 50 Backplane

If a single AC source is used it is typically connected to TRM 10 (Line), 7 (Neutral) and 4 (Ground).

Rectifier

Terminal #

Function

Terminal #

Function

Terminal #

Function

Rectifier 1

TRM2

Ground

TRM5

Line or Neutral

TRM8

Line

Rectifier 2 & 3

TRM3

Ground

TRM6

Line or Neutral

TRM9

Line

Rectifier 4 & 5

TRM4

Ground

TRM7

Line or Neutral

TRM10

Line

Chassis

TRM1

Ground

 

 

 

 

Figure 2.3-2 AC Input Wiring

Magnum VS –48 Vdc User Manual