American Sensor installation instructions Relay Module, MODEL NO. CB100, Instruction Manual

Models: CB100

1 2
Download 2 pages 42.95 Kb
Page 1
Image 1
RELAY MODULE

 

 

 

RELAY MODULE

MODEL NO. CB100

 

 

 

INSTRUCTION MANUAL

 

 

 

Page 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This manual contains instructions for installing your American SensorsTM relay module. The relay module is ULC listed as an accessory for use only with American SensorsTM interconnectable smoke alarms in the 470L, 670L and 770L series, plus models SA360, SA379, ESA5011 and combina- tion CO/Smoke alarm model COS2010.

WARNING: This relay will not operate without continuous AC power. Do not use with battery backup units.

CAUTION: Do not interconnect Model No. CB100 to any other manufacturer’s units.

RATING: 120VAC, 100mA

Use Your Relay Module For:

Sirens/Exit Signs/Bells

Warning Lights/Fire Doors/Exhaust Fans

Visual Indicators

CAUTION: THE RELAY MODULE IS NOT TO BE USED AS A METHOD OF EXTENDING THE MAXIMUM NUM- BER OF SMOKE ALARMS PERMITTED IN MULTIPLE STATION OPERATION. (REFER TO SMOKE ALARM MANUAL FOR SPECIFIED MAXIMUM LIMIT.) EACH RELAY MODULE REPLACES ONE SMOKE ALARM LOAD IN AN INTERCONNECTED STRING. THEREFORE: USE OF THE RELAY REDUCES THE MAXIMUM NUM- BER OF INTERCONNECTED SMOKE ALARMS BY ONE.

INSTALLATION INSTRUCTIONS

The CB100 relay module should be installed in a junction box. All connections should be made by a qualified electrician in accordance with the requirements of the National Electric Code and/or any local codes having juris- diction.

1.Turn off main power circuit.

2.Install and wire your compatible American SensorsTM smoke alarm as recommended in your smoke alarm owner’s manual.

3.Connect the black wires of the relay module and the smoke alarm to the black wire of the 120 VAC line.

4.Connect the interconnect wires as described below:

Your American SensorsTM CB100 relay module is easily con- figured to allow it to operate for either a CO alarm condition only, a smoke alarm condition only or for both CO and smoke alarm conditions.

To Operate For A Smoke Alarm Condition Only: See Fig. 1a and 1b on reverse.

Connect orange interconnect wire of the CB100 to the orange interconnect wire of your smoke alarm (or to the orange and brown wires of your CO/Smoke alarm).

To Operate Relay For A CO Alarm Condition Only: See Fig 2 on reverse.

Connect brown interconnect wire of the CB100 to the orange and brown wires of your co/smoke alarm and orange wire of interconnected smoke alarms.

To Operate Relay For Both Smoke Alarm And CO Alarm Conditions:

See Fig. 2 on reverse.

Open the green jumper wire on the CB100 and isolate each end using a wire nut. Connect the brown intercon- nect wire of the CB100 to the orange interconnect wire of your smoke alarm and to the orange and brown wires of your CO/Smoke alarm.

5.Connect the white wires of the relay module and the smoke alarm to the white wire of the 120 VAC line.

6.Connect the auxiliary device to the relay module contact leads as required. Both normally open and normally closed contacts are available to control the auxiliary device.

7.Cap any unused leads with a wire nut.

8.Insert the relay module into the junction box and install the faceplate.

9.Apply power to the circuit and test the smoke alarm and the auxiliary relay device for proper operation.

MODEL NO. CB100

This product is listed by

UNDERWRITER’S LABORATORIES OF

CANADA and Bears the Mark.

Dicon Global Inc.

88B East Beaver Creek Road, Unit 6, Richmond Hill, Ontario, Canada L4B 4W2 Tel: 905-482-3720 Fax: 905-731-8267

info.diconglobal.com2502-A0032REVA

Page 1
Image 1
American Sensor installation instructions Relay Module, MODEL NO. CB100, Instruction Manual, Installation Instructions