WHIRLPOOL ELECTRICAL INSTALLATION INSTRUCTIONS
All wiring must be performed by a licensed electrician in accordance with the national electrical code and all other applicable codes.
!WARNING: When using electrical products, basic precautions should always be observed, including the following:
1.DANGER: RISK OF ELECTRIC SHOCK! Connect only to a circuit protected by a
. Grounding is required. The unit should be installed by a licensed electrician and grounded.
3. Permit access for servicing motor as noted.
. All building materials and wiring should be routed away from the pump body and heater (if equipped).
PLEASE SEE THE FOLLOWING TABLE FOR GFCI CIRCUIT REQUIREMENTS:
GFCI CIRCUIT REQUIREMENTS: | FOR MODEL NUMBERS: | |
|
| |
The whirlpool should be installed on a 120 vac, 15 amp dedicated | 2422, 2425, 2645, | |
GFCI circuit. | 2771, 2805, 2908 | |
The circuit should be | ALL MODELS | |
| ||
circuit must be a three (3) wire circuit from the electrical supply panel. A | 7236, 2774 | |
grounded neutral wire and a third wire, earth ground, are essential. | MODELS ENDING IN SUFFIX | |
| ||
Optional heater requires a separate 15 amp maximum GFCI circuit. | LA, LAC, VA, VAC | |
|
| |
The whirlpool should be installed on a 120 vac, 20 amp dedicated | 6060, 2775, 2773, 2711, 2901 | |
GFCI circuit. | ||
ALL MODELS | ||
The circuit should be | ||
| ||
7236, 2774 | ||
circuit must be a three (3) wire circuit from the electrical supply panel. A | ||
grounded neutral wire and a third wire, earth ground, are essential. | MODELS ENDING IN SUFFIX | |
Optional heater requires a separate 15 amp maximum GFCI circuit. | L, LC, V, VC | |
|
|
120 VAC
WHITE |
| BLACK |
|
|
| ||
|
|
|
|
GND.
PUMP/MOTOR
ELECTRICAL DIAGRAM
READ AND FOLLOW ALL INSTRUCTIONS
WIRE SELECTION GUIDE |
|
|
|
|
| |
|
|
|
|
|
| |
|
| Maximum distance from | ||||
|
|
| fusebox to motor |
| ||
Motor |
|
|
|
|
|
|
50' |
| 100' | 150' |
| 200' | |
Hi Performance |
|
|
|
|
|
|
Rating |
|
| 115V Power Line |
| ||
2.1 H.P., |
|
|
| |||
|
|
|
|
|
| |
1.4 H.P., | 12 |
| 10 | 8 |
| 8 |
and 1.25 H.P. |
|
| ||||
|
|
|
|
|
|
The sizes shown on this
chart are recommendations
for copper conductors only. Always follow local and national electrical codes
11 |