ELECTRICAL INSTALLATION INSTRUCTIONS
All wiring must be performed by a licensed electrician in accordance with the national electrical code and all other applicable codes.
WARNING:
When using electrical products, basic precautions should always be observed, including the following:
1.DANGER: RISK OF ELECTRIC SHOCK
Connect only to a circuit protected by a
2.Grounding is required. The unit should be installed by a licensed electrician and grounded.
3.Install to permit access for servicing.
4.All building materials and wiring should be routed away from the pump body and heater (if equipped).
The whirlpool and air massage versions should be installed on a 120 vac, 15 amp dedicated circuit. The combination system requires a 120 vac, 20 amp dedicated circuit. The circuit must be a three (3) wire circuit from the electrical supply panel. A grounded neutral wire and a third wire, earth ground, are essential. ADDING THE
REQUIRES A SEPARATE 15 AMP MAXIMUM GFCI CIRCUIT.
ELECTRICAL INSTALLATION
FOR COMBINATION SYSTEM: SEPARATE 20 AMP GFCI OUTLET
FOR WHIRLPOOL OR AIR MASSAGE: SEPARATE 15 AMP GFCI OUTLET
120 VAC |
| WHIRLPOOL MOUNTED |
|
| AIR SWITCH OR |
|
| WALL TIMER |
WHITE | BLACK |
PUMP/MOTOR
GND.
ELECTRICAL DIAGRAM
READ AND FOLLOW ALL INSTRUCTIONS
(3) |