WHIRLPOOL ELECTRICAL INSTALLATION INSTRUCTIONS
All wiring must be performed by a licensed electrician in accordance with the national electrical code and all other applicable codes.
WARNING:
When using electrical products, basic precautions should always be observed, including the following:
1.DANGER: RISK OF ELECTRIC SHOCK
Connect only to a circuit protected by a
2.Grounding is required. The unit should be installed by a licensed electrician and grounded.
3.Install to permit access for servicing.
4.All building materials and wiring should be routed away from the pump body and heater (if equipped).
The whirlpool should be installed on a 120 vac, 20 amp dedicated circuit. The circuit should be
E-Z INSTALL WHIRLPOOL HEATER
ELECTRICAL INSTALLATION
INSTRUCTIONS
Install a separate 120VAC / 15AMP dedicated circuit with GFCI (Ground Fault Circuit Interrupter) protection. With a No. 8 solid copper wire, bond the heater to the homes electrical panel or approved local bonding point. A bonding lug has been provided on the heater.
At initial
SEPARATE |
|
15 AMP GFCI OUTLET | ELECTRICAL INSTALLATION |
|
120 VAC
WHITE | BLACK |
PROVERHEAT |
|
OTECTION |
|
RESET | HEATER ON |
|
| |
INSTALL | WHIRLPOOL |
| HEATER |
GND .
HEATER
1.Route two separate branch circuits (figure 1) to the junction box near the whirlpool. *Each branch circuit MUST BE GFCI PROTECTED.
2.Use copper conductors only.
3.Insure the heater and pump are properly GROUNDED and BONDED as required. Bonding connectors suitable for No. 8 AWG copper wire are located on both the pump and heater assemblies.
a.Using No. 8 AWG copper wire, bond each of these assemblies together to the homes electrical panel or approved local bonding point.
SEPARATE 20 AMP GFCI OUTLET | Fig. 1 | ||||
| for2.1 H.P. PUMP | ||||
|
| ||||
|
|
|
| ||
120 VAC |
|
|
|
|
|
W H I T E |
| B L A C K |
|
|
| ||
|
|
|
|
PUMP/MOTOR
GND .
ELECTRICAL DIAGRAM
READ AND FOLLOW ALL INSTRUCTIONS
(4) |