7. Mechanical Aquastat Wiring Diagrams

Common wiring diagrams are shown below. Select the appropriate diagram for the application. Diagrams are popular examples only. If your application is not shown, contact Amtrol Technical Support at 401.535.1216.

Boiler Controls

Typical Oil Burner (Non-Priority)

Typical Gas Valves (Non-Priority)

24V Thermostat Input (Priority)

L1

AQUASTAT

HONEYWELL

R4222D 1013

OR EQUIVALENT

DPDT RELAY

1

 

3

ZR

 

 

 

 

2

 

 

4

 

6

 

 

5

 

HYDROMAX™

 

 

 

 

COIL

 

CIRCULATOR

 

 

 

 

 

 

L1

W

Z

AQUASTAT

L1

HONEYWELL

R4222D 1013

OR EQUIVALENT B DPDT RELAY

1

 

3

 

2

 

4

 

6

 

5

HYDROMAX™

 

 

 

COIL

CIRCULATOR

 

 

 

 

L2

 

HONEYWELL

 

 

R4222D 1013

 

T

OR EQUIVALENT

T

DPDT RELAY

AQUASTAT

 

1

 

3

 

 

 

2

 

 

C1

4

 

6

 

 

 

 

 

 

 

5

HYDROMAX™

 

 

 

 

 

 

 

COIL

CIRCULATOR

L1

 

 

 

 

 

 

 

WHEN NO “ZR” TERMINAL IS AVAILABLE

GO TO THE SUPPLY SIDE OF THE HI LIMIT

L2

Zone Valves

3-Wire

4-Wire

AQUASTAT

AQUASTAT

 

 

 

 

 

24VAC

 

24VAC

 

 

 

 

END

 

 

 

 

 

SWITCH

 

 

 

 

MOTOR

 

 

 

TRANSFORMER

ZONE VALVE

ZONE VALVE

TRANSFORMER

L2

L1

END

 

 

 

 

 

L2

L1

 

 

SWITCH

 

 

 

 

Other Applications

Universal Sensor Kit

Installing Universal 10K Ohm Sensor Kit HYDROMAX models with a mechanical aquastat include a universal temperature sensor kit allowing HYDROMAX to be used with any boiler control featuring a standard “10K” DHW thermisor input (10,000 Ohms at 77° F). When installed, domestic water temperature is regulated by the boiler and the HYDROMAX aquastat is not used.

1.Unscrew and remove copper sensor bulb from sensor well.

2.Insert Universal Sensor to bottom of sensor well.

3.Plug Universal Sensor into Extension cable.

4.Connect wire leads to DHW input terminals on boiler control.

AQUASTAT

SENSOR BULB

(REMOVE)

Multi-Zone Control

AQUASTAT

Boiler Control Input

AQUASTAT

EXTENSION

L2 L1

DHW ZONE

DHW ZONE

CABLE

DHW

BOILER CONTROL

PLUG

XX TO BOILER

HYDROMAX™

CIRCULATOR

OR ZONE VALVE

HYDROMAX™ CIRCULATOR OR ZONE VALVE

UNIVERSAL SENSOR

IN SENSOR WELL

BOILER

HYDROMAX

-8-