
Program Port Connections/Wiring
The
Wiring a power connection
Use a 12
The following table shows the pinout and wiring specification information for the front panel
Program Port Connector Pinouts (RS232)
Pin | Signal | Function |
| |
1 | N/A | Not used |
| |
2 | RXD | Receive data | 1 2 3 4 5 | |
3 | TXD | Transmit data | ||
| ||||
4 | DTR | Not used |
| |
5 | GND | Signal ground |
| |
6 | DSR | Not used | 6 7 8 9 | |
7 | RTS | Request to send |
| |
8 | CTS | Clear to send |
| |
9 | N/A | Not used |
|
RJ-45 Connections
Use a standard CAT5 Ethernet cable to provide communication between the Master and external NetLinx devices.
Ethernet 10/100 Base-T Connector
The Ethernet cable provides 10/100 network connectivity between the panel and the NetLinx Master (FIG. 2).
L/A - Link/Activity LED lights |
|
|
| SPD - Speed LED lights (yellow) when |
(green) when the Ethernet |
|
|
| the connection speed is 100 Mbps |
| ||||
cables are connected and |
|
|
| and turns Off when the speed |
terminated correctly. |
|
|
| is 10 Mbps. |
FIG. 2 Layout of Ethernet LEDs
Note: DIP switch 1 activates/deactivates the Program Run Disable Mode. DIP Switches 2,3, and 4 must remain OFF at all times.
Setting the Configuration (Program Port) DIP Switch
1.Disconnect the power supply from the rear
2.Set DIP switch positions according to the information listed in the previous Baud Rate Settings table.
3.Reapply power to the unit.
SPE Port Connection/Wiring
Use an
Preparing the ME260-64 for Serial Communication
1.Launch NetLinx Studio 2.x (default location is Start > Programs > AMX Control Disc > NetLinx Studio 2 > NetLinx Studio 2).
2.Select Settings > Master Communication Settings, from the Main menu, to open the Master Communication Settings dialog box.
3.Click the Communications Settings button to open the Communications Settings dialog.
4.Click the NetLinx Master radio button (from the Platform Selection section) to indicate you are working with a NetLinx Master.
5.Click the Serial radio button (from the Transport Connection Option section) to indicate you are connecting to the Master via a COM port.
6.Click the Edit Settings button (on the Communications Settings dialog) to open the Serial Settings dialog and set the COM port parameters (used to communicate to the NetLinx Master).
7.Click the OK button three times to return to the main application.
8.
9.Assign a System Value by using Diagnostics > Device Addressing from the Main menu.
10.Enable the Change System selection by clicking on it and then enter the current and new System values.
11.Click the Change Device/System Number button and when finished click Done.
12.Select Tools > Reboot the Master Controller to access the Reboot the Master dialog, then click Reboot to restart the Master and incorporate any changes.
13.Once the dialog replies with "Reboot of system complete", click Done and then click the OnLine Tree tab in the Workspace window to view the devices on the System.The default System value is one.
14.
Baud Rate Settings
The Program Port DIP switch is located on the card’s internal circuit board. For cards installed in modules, you must remove the front panel to access the DIP switch. Use this internal DIP switch to set the baud rate used by the Program port for communication. Use this DIP switch to set the baud rate for the Program Port, according to the settings shown in the following table. Make sure the baud rate you set matches the baud rate on your PC's NetLinx COM Settings before programming the unit.
By default, the baud rate is set to 38,400 (bps).
Baud Rate Settings
Baud Rate | Position 5 | Position 6 | Position 7 | Position 8 |
|
|
|
|
|
9600 bps | OFF | ON | OFF | ON |
|
|
|
|
|
38,400 bps | OFF | ON | ON | ON |
(default) |
|
|
|
|
|
|
|
|
|
57,600 bps | ON | OFF | OFF | OFF |
|
|
|
|
|
115,200 bps | ON | ON | ON | ON |
|
|
|
|
|
Note: The Program Port DIP Switch is also used to set Program Run Disable (PRD) mode. The PRD mode prevents the NetLinx program stored in the Master from running when you power up the
Configuring the ME260-64 for Ethernet Communication
Before continuing, complete the COM port steps above.
1.Connect an Ethernet cable to the unit’s rear Ethernet connector.
2.Select Diagnostics > Network Address from the Main menu and enter the System, Device (0 for a Master), and Host Name information.
3.To configure the Address:
•Use a DHCP Address by selecting the Use DHCP radio button, then click the GET IP button (to obtain a DHCP Address from the DHCP Server), click the SET IP Information button (to retain the new address), and then finish the process by clicking the Reboot Master > OK buttons.
•Use a Static IP Address by selecting the Specify IP Address radio button, enter the IP parameters into the available fields, then click the SET IP Information button (to retain the
4.Repeat steps 1 - 5 from the previous section but rather than selecting the Serial option, choose TCP/IP and edit the settings to match the IP Address you are using (whether Static or IP).
5.Click on the Authentication Required radio box (if the Master is secured) and press the User Name and Password button to enter a valid username and password being used by the secured Master.
6.Click the OK button three times to return to the main application.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s). |
| REV: C |
|
©2006 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX.
AMX reserves the right to alter specifications without notice at any time.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com