Installation Guide
RDA-ENC2/ENC4/ENC6
Overview
The AMX Lighting™
RDA-ENC2 RDA-ENC4
Side View
(for all enclosures)
Installation Instructions
•For indoor use only.
•Mount on vertical surface only.
•Maintain 12" (304.88 mm) minimum clearance above and below the enclo- sure.
•Route class 1 conductors through upper conduit knockouts.
•Route class 2 conductors through lower conduit knockouts.
•Use 75°C (167°F) copper conductors only.
•Install filler plate
•Install only UL approved modules (see the UL Number Cross Reference to AMX Lighting ID table).
12.0" (304.8 mm)
6.0" | 12.0" |
|
|
|
|
| ||
| (152.4 mm) |
| (304.8 mm) |
|
| |||
|
|
|
| |||||
|
|
|
|
|
| 0.75" (19.05 mm) | ||
|
|
|
|
| ||||
|
|
|
|
6.0" (152.4 mm)
Enclosure Weights
•
•
•
Radia enclosures must be mounted on a vertical surface with a minimum of 12" (304.8 mm) clearance above and below the enclosure.
Configuration for |
| |
right and left | A to B | |
mounting brackets | ||
| ||
for all Radia | Top slot | |
enclosures. |
| |
| B to C | |
Maximum mounting |
| |
screw size: #12 |
| |
| Bottom slot |
FIG. 2 Bracket configuration
Dimensions between center lines (from FIG. 2):
•A to B = 5.25" (133.4 mm)
•B to C = 11.0" (279.4 mm)
•A to B = 10.0" (254.0 mm)
•B to C = 11.0" (279.4 mm)
•A to B = 16.0" (406.4 mm)
•B to C = 11.0" (279.4 mm)
18.0"
(457.2 mm)
FIG. 1 Top, front, bottom, and side views of the RDA enclosures