![](/images/new-backgrounds/1269290/2692901x1.webp)
Installation Sheet
RDM-3SWM Triple Switch Module 20A
The
Mounting points
Line in (hot)
Load out
Relay A
Relay B
Relay C
Specifications
•
•Use wires rated at 75°C (167°F)
•Torque terminals to 7
•Max. wire size: 10 AWG (4 mm²)
•Wire stripping length: 0.28" (7 mm)
•Weight: 0.95 lbs. (0.43 kg)
•BTU/hr: 5 each (15 total)
•Control current: 85 mA per relay (255 mA total) @ 12 VDC
Caution:
•All Class 1 wiring must be connected to proper terminals.
•All control wiring must be connected to proper terminals.
•Disconnect power while installing or connecting the unit.
•Keep top and bottom air bents clear at all times.
•Test loads for shots before connecting.
•Use low voltage wires with a 300 volt rating or greater.
•Use field installed copper conductors.
•All electrical ratings are for continuous duty.
•For indoor use only.
•This module may require extra power from the AXlink connection or an external power supply connected to the control card.
Connecting the RDM-3SWM to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
3
1 (+)
NOTE: The
the
FIG. 2 RDM-3SWM connections
FIG. 1 RDM-3SWM Triple Switch Module
•General purpose: 2400 W
•Resistive: 2400 W
•Ballast: 2400 W
•Motor: 277 VAC, 1 hp
Suggested Switched Loads
•Incandescent
•
•Motors
•Switched outlets
•Fluorescent