Problem

Possible Cause

Solution

 

 

 

Low battery light is on

The UPS is shut down and the

None. The UPS will return to normal

and the on-line light is

battery is discharged from an

operation when the power is restored and the

off.

extended power outage.

battery has a sufficient charge.

 

 

 

 

 

Allow the batteries to recharge for at least four

The replace battery light

Weak batteries.

hours. If the problem persists after recharging,

 

replace the batteries. See section 10.

is lit.

 

 

 

Replacement batteries not

Confirm the battery connections. See section

 

 

connected properly.

10.

 

 

 

9. Service

If the UPS requires service:

1.Use the troubleshooting section (section 8) to eliminate obvious causes.

2.Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem! See section 6.2.

3.Go to section 5.3 and perform a self-test to check the battery.

4.See the front of this manual for the correct telephone number. Call customer service for a re- turn material authorization number (RMA#). If customer service is not available in your area, call the dealer that sold the UPS.

Note the model number of the UPS, the serial number, and the date purchased. A techni- cian will ask you to describe the problem and help solve it over the phone, if possible, or will give you an RMA#.

If the UPS is under warranty, repairs are free. If not, there will be a charge for repair.

5.Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.

It is important to pack the UPS properly to avoid damage in transit. Never use styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.

Include a letter with your name, RMA#, address, copy of the sales receipt, description of the trouble, your daytime phone number, and a check (if necessary).

6.Mark the RMA# on the outside of the package. The factory cannot accept any package with- out this marking.

7.Return the UPS by insured, prepaid carrier to the address at the front of this manual.

24

Page 26
Image 26
APC 1400XLT, 3000XLT, 2200XLT user manual Service

3000XLT, 1400XLT, 2200XLT specifications

The APC (American Power Conversion) range of Uninterruptible Power Supplies (UPS) includes models such as the 2200XLT, 5000T, 1400XLT, and 3000T, each designed to meet different power protection needs in various environments. These models provide reliable backup power and surge protection, ensuring that electronic devices remain operational during utility power disruptions.

The APC 2200XLT is known for its robust performance and efficiency. This model features on-line double conversion technology, which guarantees that connected equipment receives pure sine wave power, crucial for sensitive electronics. With a power capacity of 2200 VA, the 2200XLT accommodates high-energy requirements, making it ideal for small to medium-sized businesses. The LCD display provides real-time status on power conditions, battery health, and load levels, ensuring users are always informed.

The APC 5000T, with a power capacity of 5000 VA, is designed for larger operations, providing substantial backup power for critical infrastructure. This model offers advanced features such as hot-swappable batteries, allowing maintenance without disrupting power to connected devices. The 5000T also includes PowerChute software, facilitating monitoring and management of UPS systems via a user-friendly interface. Its enhanced scalability means it can easily be expanded to meet growing power needs.

The APC 1400XLT is compact yet efficient, offering 1400 VA of power. It excels in providing reliable protection for desktop computers and workstations. Featuring Power Factor Correction (PFC), this model optimizes power delivery, resulting in increased energy savings. Its customizable alarm settings and easy-to-read LCD panel make it user-friendly, ensuring that even those with minimal technical expertise can operate it effectively.

Lastly, the APC 3000T serves as a versatile powerhouse for small to medium-sized data centers. Its 3000 VA capacity supports critical equipment, while redundant features enhance reliability. The unit is also equipped with a network management card for remote monitoring capabilities. The 3000T's ability to configure and manage multiple units in a parallel setup allows businesses to ensure that their power needs are met while maximizing uptime.

In summary, the APC 2200XLT, 5000T, 1400XLT, and 3000T UPS models offer a variety of features and technologies designed to ensure power availability and system reliability across various applications. These units emphasize security against power disturbances while providing a solid return on investment for organizations seeking to protect their critical electronic infrastructure.