14. User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

 

 

 

Every 14

Every 7 days (168

Sets the interval at which the UPS will

Automatic Self-Test

days (336

hours), On Startup

execute a self-test.

 

hours)

Only, No Self-Test

 

 

 

 

 

 

 

 

 

 

Up to eight

Use this field to uniquely identify the

UPS ID

UPS_IDEN

characters to define

UPS for network management

 

 

the UPS.

purposes.

 

 

 

 

 

Date of Last Battery

Manufactur

Date of Battery

Reset this date on battery

Replacement

Date

Replacement

replacement.

 

 

 

 

 

Minimum Capacity

 

 

The UPS will charge its batteries to

Before Return from

0 percent

15, 50, or 90 percent

the specified percentage before return

Shutdown

 

 

from a shutdown.

 

 

 

 

 

 

 

 

Set lower than normal sensitivity to

 

 

 

avoid lowered battery capacity and

Sensitivity

Normal

Reduced, Low

service life in situations where the

 

 

 

load can tolerate minor power

 

 

 

disturbances.

 

 

 

 

 

 

 

 

Sets the time before shutdown at

Duration of Low

 

 

which the UPS issues a low battery

2 minutes

5, 7, or 10 minutes

warning. Set higher than the default

Battery Warning

 

 

only if the OS needs the time for

 

 

 

 

 

 

graceful shutdown.

 

 

 

 

 

Alarm Delay After

5 second

30 second delay, At

To avoid alarms for minor power

Low Battery

Line Fail

delay

glitches, set the alarm delay.

Condition, No Alarm

 

 

 

 

 

 

 

180, 300, or 600

Sets the interval between when the

Shutdown Delay

20 seconds

UPS receives a shutdown command

seconds

 

 

 

and when shutdown occurs.

 

 

 

To avoid branch circuit overload, the

Synchronized

0 seconds

60, 180, 300 seconds

UPS will wait the specified time after

Turn-on Delay

 

 

the return of utility power before

 

 

 

turn-on.

 

 

 

 

 

High Transfer Point

253 Vac

264, 271, 280 Vac

 

 

 

 

 

 

 

Low Transfer Point

196 Vac

188, 204, 208 Vac

 

 

 

 

 

 

 

33

Page 35
Image 35
APC 1400XLT, 3000XLT, 2200XLT user manual User Configuration Items, UPS ID Upsiden

3000XLT, 1400XLT, 2200XLT specifications

The APC (American Power Conversion) range of Uninterruptible Power Supplies (UPS) includes models such as the 2200XLT, 5000T, 1400XLT, and 3000T, each designed to meet different power protection needs in various environments. These models provide reliable backup power and surge protection, ensuring that electronic devices remain operational during utility power disruptions.

The APC 2200XLT is known for its robust performance and efficiency. This model features on-line double conversion technology, which guarantees that connected equipment receives pure sine wave power, crucial for sensitive electronics. With a power capacity of 2200 VA, the 2200XLT accommodates high-energy requirements, making it ideal for small to medium-sized businesses. The LCD display provides real-time status on power conditions, battery health, and load levels, ensuring users are always informed.

The APC 5000T, with a power capacity of 5000 VA, is designed for larger operations, providing substantial backup power for critical infrastructure. This model offers advanced features such as hot-swappable batteries, allowing maintenance without disrupting power to connected devices. The 5000T also includes PowerChute software, facilitating monitoring and management of UPS systems via a user-friendly interface. Its enhanced scalability means it can easily be expanded to meet growing power needs.

The APC 1400XLT is compact yet efficient, offering 1400 VA of power. It excels in providing reliable protection for desktop computers and workstations. Featuring Power Factor Correction (PFC), this model optimizes power delivery, resulting in increased energy savings. Its customizable alarm settings and easy-to-read LCD panel make it user-friendly, ensuring that even those with minimal technical expertise can operate it effectively.

Lastly, the APC 3000T serves as a versatile powerhouse for small to medium-sized data centers. Its 3000 VA capacity supports critical equipment, while redundant features enhance reliability. The unit is also equipped with a network management card for remote monitoring capabilities. The 3000T's ability to configure and manage multiple units in a parallel setup allows businesses to ensure that their power needs are met while maximizing uptime.

In summary, the APC 2200XLT, 5000T, 1400XLT, and 3000T UPS models offer a variety of features and technologies designed to ensure power availability and system reliability across various applications. These units emphasize security against power disturbances while providing a solid return on investment for organizations seeking to protect their critical electronic infrastructure.