Stop/Start UPS and Operating the External Service Bypass

2.7.2 Switching Back the UPS to Normal Rarallel/Redundant Operation

Action

1.Set the input switch (Q001) and the output switch (Q002) to position 1.

2.Charge capacitors, connect battery, and start up the UPS as described in 2.4.1. Start UPS (from complete power down).

The UPS will automatically switch to normal operation and start load-sharing with the other parallelled UPS(s).

WARNING!

The system will discharge built-in capacitors.

ALWAYS check with a multimeter that the terminals contain no dangerous voltage before touching the system!

NOTICE!

With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed. Applicable to all bypass panels.

990-4041

18

User Guide APC Silcon 480kW 400V UPS

Page 18
Image 18
APC 480kW 400V manual Stop/Start UPS and Operating the External Service Bypass