3:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE

OR OPTIONAL SMART SLOT ACCESSORY CARDS.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-

Every 14 days

Every 7 days

Set the interval at which the UPS will

Test

(336 hours)

(168 hours),

execute a self-test.

 

 

On Startup Only,

 

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight charac-

Uniquely identify the UPS, (i.e. server

 

 

ters (alphanumeric)

name or location) for network man-

 

 

 

agement purposes.

 

 

 

 

Date of Last Bat-

Manufacture Date

mm/dd/yy

Reset this date when you replace the

tery Replacement

 

 

battery module.

 

 

 

 

Minimum Capacity

0 percent

0, 15, 30, 45, 50, 60,

Specify the percentage to which batter-

Before Return from

 

75, 90 percent

ies will be charged following a low-

Shutdown

 

 

battery shutdown before powering

 

 

 

connected equipment.

 

 

 

 

Voltage Sensitivity

High

High sensitivity,

Note: In situations of poor power qual-

The UPS detects

 

Medium sensitivity,

ity, the UPS may frequently transfer to

 

Low sensitivity

battery operation. If the connected

and reacts to line

 

 

 

equipment can operate normally under

voltage distortions

 

 

 

 

such conditions, reduce the sensitivity

by transferring to

 

 

 

 

setting to conserve battery capacity

battery operation to

 

 

 

 

and service life.

protect connected

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

Alarm Delay Con-

Enable

Enable, Mute, Dis-

Mute ongoing alarms or disable all

trol

 

able

alarms permanently.

 

 

 

 

Shutdown Delay

90 seconds

0, 90, 180, 270, 360,

Set the interval between the time when

 

 

450, 540, 630 sec-

the UPS receives a shutdown com-

 

 

onds

mand and the actual shutdown.

 

 

 

 

Low Battery Warn-

2 minutes

2, 5, 8, 11, 14, 17,

The UPS will beep when 2 minutes of

ing

PowerChute soft-

20, 23 minutes

battery runtime remains.

 

 

 

 

ware provides

(Times are approxi-

Change the low battery warning inter-

 

automatic, unat-

mate.)

val setting to the time that the operat-

 

tended shutdown

 

ing system or system software requires

 

when approxi-

 

to safely shut down.

 

mately 2 minutes

 

 

 

of battery oper-

 

 

 

ated runtime re-

 

 

 

mains.

 

 

 

 

 

 

Synchronized

0 seconds

0, 60, 120, 180, 240,

Specify the time the UPS will wait

Turn-on Delay

 

300, 360, 420 sec-

after the return of utility power before

 

 

onds

turn-on (to avoid branch circuit over-

 

 

 

load).

 

 

 

 

 

 