NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
High Transfer | 100V model: | 100V model: | Set the high transfer point higher to | |
Point | 108 Vac | 108, 110, 112, 114 | avoid unnecessary battery usage when | |
|
| Vac | the utility voltage is usually high and | |
| 120V model: | 120V model: | the connected equipment is specified | |
| to operate with input voltages this | |||
| 127 Vac | 127, 130, 133, 136 | ||
| high. | |||
|
| Vac | ||
|
|
| ||
| 230V model: | 230V model: |
| |
| 253 Vac | 253, 257, 261, 265 |
| |
|
| Vac |
| |
|
|
|
| |
Low Transfer Point | 100V model: | 100V model: | Set the low transfer point lower when | |
| 92 Vac | 86, 88, 90, 92 Vac | the utility voltage is usually low and | |
| 120V model: | 120V model: | the connected equipment is specified | |
| to operate with input voltages this low. | |||
| 106 Vac | 97, 100, 103, 106 | ||
|
| |||
|
| Vac |
| |
| 230V model: | 230V model: |
| |
| 208 Vac | 196, 200, 204, 208 |
| |
|
| Vac |
| |
|
|
|
| |
Output Voltage | 230 Vac | 220, 230, 240 Vac | Select the output voltage. | |
(230V model only) |
|
|
| |
|
|
|
|
6