Specifications

Input conductors

This product is rated 200 A. It should be supplied with a circuit breaker with a maximum rating of 200 A.

For North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 3.

For countries outside of North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 4.

Note: Input conductors are to be torqued to 31.1 Nm

(275 lb-in) using a 8 mm (5/16 in) Allen (hexagonal) wrench.

Table 1

AC Input

Nominal voltage

400 V 3 PH

 

208 V 3 PH

Frequency

47-63 Hz

Voltage configuration

3 W + N + PE

Maximum upstream circuit breaker

200 A

Maximum continuous current

160 A

Maximum continuous current with

200A

100% rated circuit breaker

 

Maximum main input conductor size

250 mcm

 

 

Table 2

AC Output

Nominal voltage

230 V/400 V 3 PH

 

120 V/208 V 3PH

Maximum continuous current

200 A

Voltage configuration

3 W + N + PE or 3 x (1 W + N + PE),

 

based on attached APC Power

 

Distribution Modules

Full load rating

138 kW @ 400 V 3PH

 

72 kW @ 208 V 3 PH

Output power cable connections

Various, based on attached APC Power

 

Distribution Modules

Output power cable lengths

Various, based on attached APC Power

 

Distribution Modules

Maximum APC Power Distribution

6

Modules

 

Maximum power distribution poles

18

 

 

Table 3

200 A, 75°C Conductors

Wiring System

Copper

Aluminum

3 CCC, 30°C Ambient

Ø&N = 3/0 AWG

Ø&N = 4/0 AWG

 

G = 6 AWG

G = 4 AWG

4 CCC, 30°C Ambient

Ø&N = 4/0 AWG

Ø&N = (2) 1/0 AWG

 

G = 6 AWG

G = (2) 4 AWG

Notes

CCC= Current-Carrying Conductors AWG = American Wire Gauge

kcmils = MCM = Thousands of Circular Mils Ø = Phase conductor

N = Neutral conductor

G = Ground (Equipment Grounding) conductor

(2) = two conductors per terminal

Table 4

200 A, Conductors

 

 

Copper, XLPE

 

 

Aluminum,

 

Copper, PVC

or EPR

Aluminum,

XLPE or ERP

Install.

Insulation,

Insulation,

PVC Insulation, Insulation,

Method 30°C Ambient

30°C Ambient 30°C Ambient

30°C Ambient

B1

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

150 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 95 mm²

PE = 50 mm²

B2

Ø&N = 120 mm² Ø&N = 95 mm² Ø&N =

240 mm² Ø&N =

120 mm²

 

PE = 70 mm²

PE = 50 mm²

PE = 120 mm²

PE = 70 mm²

C

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

150 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 95 mm²

PE = 50 mm²

E

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

120 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 70 mm²

PE = 50 mm²

F

Ø&N = 70 mm²

Ø&N = 50 mm² Ø&N =

95 mm²

Ø&N =

70 mm²

 

PE = 35 mm²

PE = 25 mm²

PE = 50 mm²

PE = 35 mm²

Notes

Ø= Phase conductor N = Neutral conductor

PE = Protective Earth conductor PVC = Polyvinyl-chloride XLPE = Cross-linked polyethylene EPR = Ethylene propylene rubber