Physical Dimensions, Environment and Compliance

Regulatory Agency Approval

Physical Dimensions

Dimensions (HxWxD)

Unit: 229 x 457 x 737 mm (9 x 18 x 29 in)

 

Shipping: 406 x 610 x 889 mm (16.5 x 24 x 36 in)

Weight

Unit: 23.5 kg (52 lb)

 

Shipping: 34 kg (75 lb)

 

Environment and Compliance Section

 

 

Operating Environment

Protected from water and conductive contaminants

Temperature

Operating: 0 to 30°C (32 to 86° F)

 

Operating (derated): 0 to 40ºC (32 to 104ºF)

j

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference, when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Guide, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

This Class A digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe A est conforme à la norme NMB- 003 du Canada.

 

Storage: 0 to 45°C (32 to 113°F)

Humidity

Operating: 0 to 95%, non-condensing

 

Storage: 0 to 95%, non-condensing

Certification

Certified by VDE to IEC 60439-1

Conditional Short-Circuit

10 kA

Current Rating (ICC)

 

Rated Impulse Withstand

4 kV

Voltage (UCC)

 

Rated Diversity Factor

0.7

 

 

Note: APC’s products, similar to most computing products, are designed to operate in an environment from 0 to 40°C. Most data centers will maintain an operating temperature between 0 to 30°C. Conductor Ampacity tables of the National Electrical Code (NFPA 70) and IEC 60364-5-53 are based on an environment from 0 to 30°C. If this product is installed in an environment greater than 30°C, either this product’s current rating will have to be derated, or the cross sectional area of the conductors supplying it will have to increase, in accordance with the derating factors of NFPA 70 and IEC 60364-5-53.

This is a Class A Product. In a domestic environment this product may cause interference in which case the user may be requires to take adequate measures.

APC Worldwide Customer Support

For local, country-specific centers: go to www.apc.com/support/contact.

4

Page 4
Image 4
APC 990-3051C-001 Regulatory Agency Approval, APC Worldwide Customer Support, Physical Dimensions