InRow RC/RD/RP (600 mm) User’s Guide50
– Click on any e-mail recipient or trap receiver, and specify any value up to three digits to
configure the following detailed options:
• How long, in seconds or minutes, the cooling unit waits after the event occurs before
sending e-mail to the selected e-mail recipient or a trap to the selected trap receiver. If the
event clears during this delay period, no notification is sent. To configure a delay longer
than 999 seconds (16 minutes, 39 seconds), use minutes.
How frequently to send e-mail to the selected e-mail recipient or a trap to the selected trap
receiver. E-mail or a trap repeats at the time interval specified here in seconds, minutes, or
hours, unless the event has cleared.
The number of times to send e-mail to the selected e-mail recipient or a trap to the selected
trap receiver. Choose to send e-mail or a trap a specified number of times or to repeat the
notification an unlimited number of times. In either case, notification stops if the event
clears.
When configuring events, you can enable or disable notification to configured
e-mail recipients, Syslog servers, or trap receivers, but you cannot add or
remove any recipients, receivers, or Syslog servers. To add or remove
recipients, receivers, or servers, see “Syslog” on page 27, “E-mail recipients”
on page 53, and “Trap receivers.” on page 54