InRow RC/RD/RP (600 mm) User’s Guide70
Press ENTER. The screen displays uppercase C, indicating transfer mode.
9. From the terminal program’s menu, select the binary AOS file to transfer via XMODEM-CRC.
After the XMODEM transfer is complete, set the baud rate to 9600 (if you selected a different
rate in step 8). The cooling unit automatically restarts.
10.Repeat step 4 through step 9 to install the application module. In step 9, use the application
module file name, not the AOS module file name.
For information about the file name format used for application modules, see
“Firmware files” .