Installing Equipment

Installing Equipment

Vertical Mounting Flange Cutouts WARNING

TIP HAZARD

This cabinet is easily tipped. Follow the precautions below during and after equipment installation.

Make sure you have secured the cabinet to the floor before installing equipment.

Install the heaviest equipment first toward the bottom of the cabinet to prevent the cabinet from becoming top-heavy.

Do not extend equipment on sliding rails until you have installed 158 kg (350 lbs) of equipment into the bottom of the cabinet for stability or until you have installed the bolt-down brackets. Do not extend more than one piece of equipment on sliding rails at a time.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

To install rack-mount equipment in the cabinet:

1.Review the equipment manufacturer’s installation instructions.

2.Locate the top and bottom U-space on the vertical mounting rails. Every third hole on the mounting rail is numbered to indicate the middle of a U-space.

3.Install the cage nuts on the interior of the vertical mounting rail; then install the equipment. (To remove a cage nut, squeeze the sides to release it from the square hole.)

Vertical Mounting Flange Cutouts

NetShelter SV 800 mm (31.5 in.) wide cabinets have removable vertical mounting flange cutouts along the sides. When removed, side airflow is increased. Other airflow and cable management options exist. Please visit the website (www.apc.com) for other options and more information.

ns2017a

NetShelter SV User Manual

17