ConnectRelayCommunicationCard

RelayCommunicationCardContacts

Therelaycommunicationcardcontainssixprogrammabledrycontactoutputsandtwoprogrammable
dryinputsandisstandardontheMGEGalaxy4000.Theinputsandoutputsarefactoryprogrammed
accordingtofunctionslistedintablebelow.
InputsFactorySettingsOptions(availableonbothcontacts)
1.AUPSON
1.BUPSOFF
Roomtemperaturefault
Transfertobypassdisabled
TransfertobypassdisabledifbypassACsourceoutof
tolerance
DesynchronizeUPSfrombypassACsource
OutputsFactorySettingsOptions(availableonallcontacts)
1.1Generalalarm
1.2Batteryfault
1.3LoadonUPS
1.4Loadonautomatic
bypass
1.5Loadonbatterypower
1.6Lowbatterywarning
Overload
PFCFault
Inverterfault
Chargerfault
Automaticbypassfault
BypassACsourceoutoftolerance
Battery-temperaturefault
Emergencypoweroffactivated
Batterycircuitbreaker(s)open
Phase-sequencefaultonnormalorbypass
ACsource
Blownfuse(s)
TransfertobypassACsourcedisabled
OperationinECOmode
UPSonbypassACsource
Theoutputcontactsnumbersforasecondrelayboardinstalledwillbe2.1to2.6.Contactsareof
theNO(normallyopen)type.Fordrycontactssettingsee“MGEGalaxy400040–75kVA208V
OperationManualUserCongurationSettingsScreen“.
Caution:Isolateandlock-outallpowersourcesforthiscardbeforemakingconnections.
NeverconnectELSV(extralowsafetyvoltage)andnon-ELSVcircuitstothedifferent
outputsofthesamecard.
16MGEGalaxy400040–75kV A208V990–3964–001