Precautions

Precautions

Precautions

 DANGER DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.

This equipment must only be installed and serviced by qualified electrical personnel.

Turn off all power supplying this equipment before working on or inside equipment.

Always use a properly rated voltage sensing device to confirm power is off.

Replace all devices, doors and covers before turning on power to this equipment.

This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.

Failure to follow these instructions will result in death or serious injury.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH WARNING

INADEQUATE GROUNDING HAZARD

Do not use on ungrounded systems.

Failure to follow these instructions can result in death or serious injury.

INADEQUATE GROUNDING HAZARD CAUTION

LOSS OF SURGE SUPPRESSION

Turn off all power supplying the equipment and isolate the Surge

Protective Device before Megger® or hi-potential testing.

Failure to follow these instructions can result in equipment damage.