Replacing the Battery
This UPS has an easy to replace
Note: Please read the cautions in the APC Safety Guide.
Once the battery is disconnected, the loads are not protected from power outages.
Battery Replacement Procedure - 2200 - 3000 VA Models | Battery Replacement Procedure - 450 - 1400 VA Models |
1.Grasp the top edge of the bottom front cover and tilt it out.
2.Unhook the bottom section of the front cover from the chassis and set it aside.
3.Use a
4.Grip the wires for the front set of batteries and pull firmly to disconnect the connector from the battery compartment.
5.Pull the white cord on the front battery connector to remove the batteries.
6.Set aside the foam spacer located between the batteries.
7.Reach into the battery compartment and grasp the white cord on the other battery connector. Pull firmly to disconnect the connector and remove the second set of batteries.
Note: Be careful removing the batteries - they are heavy.
8.Slide the first set of new batteries into the unit. Hold the connector down below the top of the batteries and toward the door, otherwise the assembly will not fit. Guide the connector over the top of the batteries and press firmly to connect it to the rear connector of the battery compartment.
Note: Small sparks at the battery connectors are normal during connection.
9.Set the foam spacer against the rear batteries to prevent the wires from being pinched.
10.Slide the second set of batteries in, then guide the connector over the batteries and press firmly to connect it to the front connector of the battery compartment.
11.Close the battery door, replace the screws, and replace the lower front cover. 12.Dispose of the old battery properly at an appropriate recycling facility or return
it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
1400 VA
450 - 1000 VA
1.Grasp the top of the front cover and tilt it out and down.
2.Unhook the bottom of the cover from the chassis and lift it upward to expose the battery door. Be careful not to strain the ribbon cable. Do not touch the exposed printed circuit board.
3.Fold the front cover on top of the UPS as shown.
4.Use a
Grasp the tab and gently pull the battery out of the UPS.
5.Disconnect the battery leads.
For the 450 through 1000 VA models, loosen the connectors by gently
wiggling them while pulling straight back from the battery connector.
For the 1400 VA model, pull the two gray couplers apart to disconnect the battery.
6.Connect the battery leads to the new battery.
Note: Small sparks at the battery connectors are normal during connection.
For the 450 through 1000 VA models, connect the red wire to the positive (+)
terminal and the black wire to the negative
For the 1400 VA model, connect the gray battery coupler to the UPS’s coupler.
7.Slide the battery into the UPS.
8.Close the battery door, replace the battery compartment screws, and replace the front cover.
9.Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory | User Selectable Choices | Description |
| Default |
|
|
|
|
|
|
Automatic | Every 14 days | Every 7 days (168 hours), | Sets the interval at which the UPS |
| (336 hours) | On Startup Only, No Self- | will execute a |
|
| Test |
|
|
|
|
|
UPS ID | UPS_IDEN | Up to eight characters to | Use this field to uniquely identify the |
|
| define the UPS. | UPS for network management |
|
|
| purposes. |
|
|
|
|
Date of Last Battery | Manufacture | Date of Battery | Reset this date on battery |
Replacement | Date | Replacement | replacement. |
|
|
|
|
Minimum Capacity Before | 0 percent | 15, 50, 90 percent | The UPS will charge its batteries to |
Return from Shutdown |
|
| the specified percentage before return |
|
|
| from a shutdown. |
|
|
|
|
Sensitivity | Normal | Reduced, Low | Set lower than normal sensitivity to |
|
|
| avoid lowered battery capacity and |
|
|
| service life in situations where the |
|
|
| load can tolerate minor power |
|
|
| disturbances. |
|
|
|
|
Duration of Low Battery | 2 minutes | 5, 7, 10 minutes | Sets the time before shutdown at |
Warning |
|
| which the UPS issues a low battery |
|
|
| warning. Set higher than the default |
|
|
| only if the OS needs the time for |
|
|
| graceful shutdown. |
|
|
|
|
Alarm Delay After Line Fail | 5 second delay | 30 second delay, At Low | To avoid alarms for minor power |
|
| Battery Condition, No | glitches, set the alarm delay. |
|
| Alarm |
|
|
|
|
|
Shutdown Delay | 20 seconds | 180, 300, 600 seconds | Sets the interval between when the |
|
|
| UPS receives a shutdown command |
|
|
| and when shutdown occurs. |
|
|
|
|
Synchronized | 0 seconds | 60, 180, 300 seconds | To avoid branch circuit overload, the |
|
|
| UPS will wait the specified time after |
|
|
| the return of utility power before |
|
|
| |
|
|
|
|
High Transfer Point | 132 VAC | 135, 138, 129 VAC | To avoid unnecessary battery usage, |
|
|
| set the High Transfer Point higher if |
|
|
| the utility voltage is chronically high |
|
|
| and the load is known to work well |
|
|
| under this condition. |
|
|
|
|
Low Transfer Point | 103 VAC | 100, 97, 106 VAC | Set the Low Transfer Point lower if |
|
|
| the utility voltage is chronically low |
|
|
| and the load can tolerate this |
|
|
| condition. |
|
|
|
|
For Computer Interface Port Specifications, see the APC Website (www.apcc.com).
Service
If the UPS requires service do not return it to the dealer!
Follow these steps:
1.Use the Troubleshooting section of the Quick Reference Guide to eliminate common problems.
2.Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem!
3.If the problem persists, call customer service or visit the APC Internet Website (www.apcc.com).
Note the model number of the UPS, the serial number, and the date purchased. A technician will ask you to describe the problem and try to solve it over the phone, if possible. If this is not possible the
technician will issue a Return Merchandise Authorization Number (RMA#).
If the UPS is under warranty, repairs are free. If not, there is a repair charge.
4.Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.
Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.
Include a letter with your name, RMA#, address, copy of the sales receipt, description of the trouble, your daytime phone number, and a check (if necessary).
5.Mark the RMA# on the outside of the package.
6.Return the UPS by insured, prepaid carrier to the address given to you by Customer Service.
North & Latin America | Europe |
APC | APC |
132 Fairgrounds Road | Ballybritt Business Park |
West Kingston, Rhode Island 02892 USA | Galway, Ireland |
Internet | |
http://www.apcc.com | apctech@apcc.com |
Specifications
| 450 VA | 700 VA | 1000 VA |
| 1400 VA |
| 2200 VA |
| 3000 VA | |
Acceptable input voltage |
|
|
| 0 - 160 VAC |
|
|
|
| ||
Output voltage |
|
|
|
|
|
| ||||
Input Protection |
|
| Resettable circuit breaker |
|
|
|
| |||
Frequency limits |
|
| 50 or 60 Hz, ±5% |
|
|
|
| |||
Transfer time |
|
| 2 ms typical, 4 ms maximum |
|
| |||||
Maximum load | 450 VA | 700 VA | 1000 VA |
| 1400 VA |
| 2200 VA |
| 3000 VA | |
| 280 W | 450 W | 670 W |
| 950 W |
|
| 1600 W |
| 2250 W |
|
|
| 115 VAC |
|
|
|
| |||
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout. | ||||||||||
|
|
|
|
|
| |||||
Protection | Overcurrent and | |||||||||
Noise Filter | Normal and common mode EMI/RFI suppression, 100 kHz to 10 MHz | |||||||||
Battery type |
| Spill proof, maintenance free, sealed |
|
| ||||||
Typical battery life | 3 to 6 years, depending on number of discharge cycles and ambient temperature | |||||||||
Typical recharge time |
|
| 2 to 5 hours from total discharge |
|
| |||||
Operating temperature |
|
| 0 to +40 ºC (+32 to +104 ºF) |
|
| |||||
Storage temperature |
|
|
|
| ||||||
Operating and storage relative |
|
| 0 to 95%, |
|
|
|
| |||
humidity |
|
|
|
|
|
|
|
|
|
|
Operating elevation |
|
| 0 to +3,000 m (0 to +10,000 ft) |
|
| |||||
Storage elevation |
|
| 0 to +15,000 m (0 to +50,000 ft) |
|
| |||||
Electromagnetic immunity |
|
| IEC |
|
|
|
| |||
Audible noise in dBA at 1 m (3 ft) | <41 | <42 |
| <45 |
|
|
| <53 | ||
Size (H x W x D) | 15.8 x 13.7 x 35.8 cm | 21.6 x 17 x 43.9 cm (8.5 x |
| 43.2 x 19.6 x 54.6 cm (17.0 | ||||||
| (6.2 x 5.4 x 14.1 in.) | 6.7 x 17.3 in.) |
|
| x 7.7 x 21.5 in.) | |||||
Weight - net (shipping) | 10.5 | 13.1 | 18.8 |
| 24.1 (26.1) |
| 51 (60.8) |
| 55.8 (64.4) | |
| (11.8) | (14.5) | (20.8) kg |
| kg |
|
| kg |
| kg |
| kg | kg | 41.5 (46) |
| 53 (58) lb. |
| 112 (134) |
| 123 (142) | |
| 23.2 | 29 (32) | lb. |
|
|
|
| lb. |
| lb. |
| (26) lb. | lb. |
|
|
|
|
|
|
|
|
Safety approvals |
| Listed to UL 1778, certified to CSA 107.1 |
|
| ||||||
EMC verification |
| FCC/DOC Class B certified |
| FCC/DOC Class A | ||||||
|
|
|
|
|
|
|
|
| verified |