II. specifications
Dimensions: 20 3/4” W x 24” L x 20 3/8”– 23 5/8” H
Weight: 93 lbs.
Capacity: 90 pints per day @ 60%RH, 80˚F (ANSI/AHAM
Power: 115 VAC, 8 Amps, Unit is equipped with an 8 ft. grounded cord.
Design Airflow: 275 CFM @ 0.6 in. w.c.
Filter: MERV 8 Filter
Cabinet Insulation: 1” foil faced EPS insulation
Inlet Air Operating Conditions: 40˚F to 105˚F
Ambient Air Operation Conditions: 40˚F to 150˚F
IV. operating instructions
Use the main control knob (Figure 2) on the outside of the unit to set the dehumidifier dryness setting. Start with a “Normal” setting for most installations. Moving the knob clockwise to “more” will make conditions drier. Moving the knob toward “less” allows for higher moisture levels.
Based on the indoor temperature, use the following table to determine the control knob setting to reach the desired RH value. The dehumidifier will work to achieve these values.
FIGURE 2
III.installation instructions
1.Install the drain line
NOTE: The provided condensate trap must be installed to the dehumidifier.
•Verify the bottom of the dehumidifier is 2 1/2” or higher above the floor.
•Insert the high side of the trap into the drain outlet (water flow direction is shown on the trap and should point away from the dehumidifier)
•If there is not enough room to install the trap directly into the dehumidifier, use the provided 90° elbow to position the trap close to the dehumidifier
%RH (± 5%) based on Control Knob Setting and Indoor Temperature
Control Knob |
| Indoor Temperature |
| ||
| Setting | 65°F | 70°F | 75°F | 80°F |
1 | – “LESS” |
| 84% | 71% | 60% |
2 |
| 86% | 73% | 61% | 52% |
3 | – “NORMAL” | 74% | 63% | 53% | 45% |
4 | – “NORMAL” | 64% | 54% | 45% | 39% |
5 | – “NORMAL” | 55% | 46% | 39% | 33% |
6 |
| 47% | 39% | 33% | 28% |
7 | – “MORE” | 40% | 34% | 28% | 24% |
Example: At an indoor temperature of 75°F with a dehumidifier control knob setting of 3, the dehumidifier will work to achieve an RH value of 53%.
NOTES:
1.%RH values are ±5% and are to be used as a GUIDE ONLY for initial
2.Indoor Temperature is measured at the inlet to the dehumidifier.
IMPORTANT: The bottom of the trap outlet must be at least 1/2 inch below the bottom of the dehumidifier to ensure a proper drainage slope (see Figure 1).
•After verifying that the trap is in the proper orientation, use PVC primer and cement to secure the trap in place. Cement the supplied threaded coupler to the outlet of the trap.
•Screw the supplied hose barb fitting into the coupler and attach the supplied 1/2 inch I.D. drain hose. Route the hose to the nearest drain.
IMPORTANT: To prevent a pressure lock within the drain line, the tube must be installed with a constant downward slope.
Prime the drain system by filling the drip pan in the dehumidifier with water until flow is completed to the drain.
2. Plug the dehumidifier directly into an outlet – do not use an extension cord. | |||
NOTE: A 15 amp circuit is required for proper operation. |
|
| |
3. Turn the ON/OFF switch to ON. |
|
|
|
4. System Checkout: |
|
| FIGURE 1 |
• Rotate the control knob clockwise to |
| BARBED FITTING |
|
the “Test” position. |
|
| |
| COUPLER |
| |
|
|
| |
a. The blower will start immediately |
| TRAP | 1/2” |
and after three minutes the |
|
|
|
compressor will start. |
|
|
|
b. Both will run for one minute then |
| W | |
| ER FLOW | ||
|
| A |
|
|
| T |
|
both will shut off. |
|
| |
|
|
|
c. Turn the control knob to the desired setting.
• If the unit does not run, refer to the Troubleshooting Guide.
V. Troubleshooting guide
SYMPTOM | TROUBLESHOOTING PROCEDURE / POSSIBLE REASON | |
|
| |
| • Reheat of outgoing air will cause a temperature increases across the dehumidifier | |
Dehumidifier is producing hot air | • Unit will possibly run continuously initially. After unit has “dried” home, dehumidifier | |
| will cycle, reducing load | |
| • Unit will need time to “dry” materials in home before effectively changing RH. | |
Dehumidifier not adequately dehumidifying | • Compressor is not turning on | |
| • System undercharged | |
Dehumidifier is not draining properly | • Check condensate trap to be sure it is clear | |
• Check drain line for continuous slope | ||
| ||
| • Follow all of the system checkout procedures. Make sure power switch is on! | |
Dehumidifier does not run | • Check that circuit breaker is not tripped. The dehumidifier requires a minimum of | |
| 8 amps. The dehumidifier should be placed on its own dedicated 15 amp circuit |
LED CODES
Green LED
Activity | Status | |
ON Solid | Compressor ON | |
Blinking 1 second on, 1 second off | Sampling | |
Blinking 1/2 second ON, 1/2 second OFF | Defrosting | |
|
| |
Red LED |
| |
Activity | Status | |
1 | Blink every 5 seconds | There is an error with the RH sensor |
2 | Blinks every 5 seconds | The board temperature sensor is opened or shorted |
3 | Blinks every 5 seconds | The Model 70 Living Space Control fails to respond after 3 consecutive attempts |
4 | Blinks every 5 seconds | The refrigerant charge has been detected as low |
5 | Blinks every 5 seconds | The temperature sensor is out of the operating range |
6 | Blinks every 5 seconds | The internal frost sensor is opened or shorted |
7 | Blinks every 5 seconds | The float switch has opened |
Test Mode
At the end of test mode (3 minutes of DEH Fan + 1 minute of Compressor ON & DEH Fan), the Red and Green LEDs will turn ON and OFF alternately until the knob has been turned away from “TEST”.