Ducting
The dehumidifier is supplied with two 8” round collars. An integral backflow damper is installed in the outlet collar. In a ducted installation, the dehumidifier pulls air from the living space or HVAC return duct and supplies the dehumidified air to the HVAC supply duct (See Figures 5, 6 & 7).
Ducted Installation
•Move supply collar to the desired location, if necessary. (See Supply Collar in
•The unit can be ducted to the supply or both the return and supply. The dehumidifier inlet ducting must be a minimum of 6” upstream of the
HVAC system air cleaner and the outlet must be ducted a minimum of 6” downstream of the cooling coil.
•Use the least amount of ductwork possible. To ensure best performance, do not exceed a total of 50 feet of duct installed in accordance with
SMACNA Standards. UL approved, 8” diameter, insulated duct is recommended for all connections.
• All joints and seams must be sealed.
Figure 5 – Basement Installation
Figure 6 – Equipment Room/Closet Installation
DEHUMIDIFIED AIR IS SUPPLIED |
| |
DOWNSTREAM FROM | ||
MINIMIZE EVAPORATION OFF | ||
| ||
SUPPLY DUCT |
| |
| RETURN | |
| DUCT | |
HVAC / FURNACE |
| |
115 VAC | AIR IS PULLED | |
DEDICATED | FROM MAIN | |
CIRCUIT | RETURN DUCT | |
DEHUMIDIFIER | DEHUMIDISTAT WITH | |
| ||
| SET POINT KNOB | |
CONDENSATE HOSE |
| |
(TO COMMON DRAIN OR OUTSIDE) |
|
SUPPLY DUCT
HVAC / FURNACE
DEHUMIDIFIED AIR IS SUPPLIED
DOWNSTREAM FROM
MINIMIZE EVAPORATION OFF
115 VAC
DEDICATED
CIRCUIT
DEHUMIDIFIER
CONDENSATE HOSE ON DEHUMIDIFIER (TO COMMON DRAIN OR OUTSIDE)
Figure 7 – Attic Installation
| MAIN SUPPLY DUCT | |
| HVAC EVAPORATOR COIL | |
DEHUMIDIFIER | HVAC/FURNACE SYSTEM | |
SHOWN IN HORIZONTAL | ||
DEHUMIDIFIED AIR IS SUPPLIED | ORIENTATION | |
| ||
DOWNSTREAM FROM EVAPORATOR COIL |
| |
TO MINIMIZE EVAPORATION OFF COIL | MAIN RETURN | |
115 VAC | ||
DUCT | ||
DEDICATED | ||
| ||
CIRCUIT |
| |
AIR FILTER |
| |
ACCESS |
| |
DOOR | CONDENSATE | |
| ||
RELOCATE DEHUMIDISTAT | HOSE | |
(TO COMMON | ||
TO LIVING SPACE | ||
DRAIN OR | ||
| ||
| OUTSIDE) | |
PRINCIPAL |
| |
LIVING SPACE |
|
Note 1: Attic installations require the following.
1.The dehumidistat must be removed from the unit and relocated in the living space. An insulated cover plate is provided to cover the dehumidistat opening.
2.The dehumidifier must be installed in a secondary drain pan with a float switch.
Note 2: Vibration isolators placed under the dehumidifier feet are recommended when the dehumidifier is installed on ceiling joists.
3