Aprilaire 65 Table of Contents, Materials Provided, Overview, Location Recommendations, Checkout

Models: 65

1 7
Download 7 pages 1.12 Kb
Page 2
Image 2
Table of Contents

Table of Contents

 

MATERIALS PROVIDED

 

 

 

Safety Instructions

1. . . . System. .

Checkout

 

 

 

Overview

 

 

Power Up

. . . 9

 

.2

 

. .

 

.10

Specifications

 

 

Test Mode

 

. 2

 

.

.

10

 

 

 

Humidity Setting

Materials Provided

 

.3 . . . . . Offset

.

.

10

Location Recommendations

3. . .

Turning On and Setting Control . .

. .

 

. 11. .

Sequence of Operation

. . . 11. . . .

Installation

 

 

 

 

Troubleshooting

 

 

 

Mount Control

 

4

 

 

 

 

Error Codes

. .

 

. 11

Wiring

 

 

 

 

5

 

. .

 

.12. . . .

 

 

 

Troubleshooting Guide

 

MATERIALS PROVIDED

 

MATERIALS NOT PROVIDED

Wall-Mount Control

 

• Wires

• Mounting Screws

 

• Wire Nuts

• Drywall Anchors

 

 

• RH Setting Label

 

 

A self-adhesive label (RH Setting Label) showing recommended RH settings based on outdoor temperature is provided.. The label can be attached to the front of the control to serve as a guideline and a reminder for the homeowner to adjust the RH setting as outdoor temperature changes..

OVERVIEW

LOCATION RECOMMENDATIONS

The Aprilaire® Model 65 Humidifier Control provides control of the humidifier from the living space.. The control allows the homeowner to set and adjust the humidity setting and turn the humidifier on or off from a convenient location.. The Model 65 uses an onboard sensor to monitor the relative humidity in the space in which it is located and displays the measured relative humidity on the digital display..

SPECIFICATIONS

ELECTRICAL

MOUNT CONTROL

In an area the homeowner wants to monitor and control moisture levels..

On an interior wall.

Approximately 5’ off the floor.

At least 18” from an outside wall.

See Figure 1..

DO NOT MOUNT CONTROL

In the flow of a supply register.

Behind doors, in corners or other dead air spaces.

In direct sunlight, near lighting fixtures, or other appliances that give off heat..

On an outside or unconditioned area wall.

In stairwells or near outside doors.

On a wall with concealed pipes or ductwork.

Input Voltage and Current

Voltage: 24V AC +/-20%

 

Current: 25mA (nominal), 50mA (max..) at 24V AC

 

 

Output

Dry Contact, Normally Open – H Terminals

 

 

 

 

CONTROL

 

 

 

Humidity Setting Range

10% – 50% RH

 

 

Accuracy

+/-5% RH

 

 

Differential

3%

 

 

Low Temp

40°F

 

 

High Temp

99°F

 

 

Figure 1 – Mounting Location

90-1666

2

3

Page 2
Image 2
Aprilaire 65 Table of Contents, Materials Provided, Overview, Location Recommendations, Specifications, Checkout