Aprilaire model 800 specifications Display Panel, Function

Models: model 800

1 32
Download 32 pages 36.22 Kb
Page 12
Image 12
Display Panel

Display Panel

TABLE 4 – Display Panel

Icon

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

Main switch.. Press to turn humidifier on and off..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resets timer for start-up water conditioning..

 

 

 

 

 

 

 

Light

Solid green when humidifier is turned on..

 

Flashes green for one minute once power is restored if humidifier was operating when power was shut off..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fill valve indicator..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid green during normal operation when canister water is being replenished..

Light

 

Flashes green (along with Drain light) indicating fill and drain valves are pulsing to dislodge mineral deposits..

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid red if canister needs water but water is not detected.. See Troubleshooting Guide..

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates call for humidity..

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid green during call for humidity..

 

 

 

 

 

 

 

Light

Solid yellow if humidifier cannot reach nominal output within first 48 hours of operation due to insufficient water conductivity..

 

 

 

 

 

 

Humidifier will continue to cycle valves in an attempt to reach capacity for an additional 48 hours.. Approximately 1/10

 

 

 

 

 

 

teaspoon of table salt can be added to fill cup to increase conductivity of water..

 

 

 

 

 

 

 

 

 

 

 

 

 

Drain valve indicator..

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid green to indicate start of drain cycle..

 

 

 

 

 

 

Drain cycle occurs:

 

 

 

 

 

 

1) To maintain nominal steam output during normal operation..

 

 

 

 

 

 

2) During end of season shut down.. (End of season shut down occurs after 72 hours of inactivity..)

Light

3) If humidifier has operated for 168 hours without a drain cycle..

4) When humidifier is turned off..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashes green (along with fill light) indicating drain and fill valves are pulsing to dislodge mineral deposits..

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashes green when humidifier is turned off indicating canister is draining.. When flashing stops, main power disconnect

 

 

 

 

 

 

can be turned off and front panel can be opened..

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates canister needs to be replaced or humidifier requires other type of service..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashes red when canister can no longer supply demand and needs to be replaced because electrodes have been corroded

 

 

 

 

 

 

or coated with mineral deposits.. Humidifier may continue to generate steam but at a reduced capacity..

 

 

 

 

 

 

 

Light

Flashes red if humidifier with new canister cannot generate steam due to insufficient water conductivity after 96 hours of

drain/fill activity.. Approximately 1/10 teaspoon of table salt can be added to fill cup to increase conductivity of water..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid red if controller detects over-current between electrodes.. Causes may include electrodes coated with mineral

 

 

 

 

 

 

deposits, blocked drain, or defect in drain valve circuit.. See Troubleshooting Guide..

 

 

 

 

 

 

 

12