Winterizing Procedure:

1.Disconnect all electrical power to the heater; turn OFF circulating pump.

2.At the two (2) water connection unions, disconnect the plumbing to the heater (removal is counterclockwise).

3.Locate the drain plug at lower, right-hand, front corner of heater. (See Figures 1 & 2, below.)

4.Using a 5/8", box-end wrench, remove the drain plug (removal is counterclockwise).

5.Permit all of the water to drain out of the condenser, and then replace the plug: thread the plug in clockwise until just snug, then apply an additional 1/8 turn.

6.To prevent insects and vermin from entering the plumbing during the winterized period, partially reconnect the two (2) plumbing connection unions: couple each union one or two threads; this will permit condensation to drain, but will prevent most insects and animals from entering the plumbing circuit.

7.Next Season: to ready the heat pump for use, simply retighten plumbing connection unions. Hand-tight is generally sufficient.