4.4 TEST FOR SPILLAGE

A test for spillage must be made before the installed fire is left with the user. This is carried out in the following manner. Light the fire and leave at HIGH rate. Close all the doors and windows in the room and after the fire has been alight for five minutes insert a lighted smoke match in line with the bottom edge of the canopy and 10mm below it (See Fig. 8). Hold the match with a pair of pliers or in a metal tube. If all of the smoke is drawn into the fire the installation is satisfactory. if in doubt, repeat the test after a further ten minutes.

If there is a fan or a fan operated appliance in a connecting room then the spillage test must be repeated with the fan running and all inter-connecting doors between the fan and the fire left open. If the fan and the fire are in the same room, close all windows and doors connected to the room. Switch on the fan and repeat the spillage test.

If spillage is detected, inspect the sealing of the fire to the surround / hearth. If this is satisfactory proceed as follows:

If a spigot restrictor was fitted, disconnect the fire and remove the spigot restrictor. Re-install the fire and repeat the above spillage test. If there is still evidence of spillage then there may be a fault with the chimney or insufficient air in the room. if the cause of the spillage cannot be corrected DISCONNECT THE FIRE AND SEEK EXPERT ADVICE.

Fig. 8

10.0

25.0

SMOKE MATCH

AIRBOX SIDE

1.FIT CASE.

2.LIGHT FIRE AND LEAVE AT FULL RATE

3.CLOSE ALL DOORS AND WINDOWS

4.AFTER 5 MINUTES INSERT SMOKE MATCH AS SHOWN IN THE DIAGRAM.

5.SMOKE WILL BE DRAWN INTO THE FIRE IF INSTALLATION IS SATISFACTORY.

6.IF SPILLAGE OCCURS, WAIT FOR 10 MINUTES AND REPEAT THE TEST.

7.IF SPILLAGE IS STILL EVIDENT PROCEED AS IN FITTERS INSTRUCTIONS.

4.5 CHECK IGNITION

Check that ignition of the pilot and the cross lighting to the main burner is satisfactory.

NB. The spark gap between the electrode and thermocouple tip should be between 3.0 and 5.0mm (See Fig. 9).

4.6 CHECK OPERATION OF FSD

Leave the fire running on HIGH rate for 5 minutes and then turn off the gas at the service cock. After 3 minutes turn the service cock on again. If the gas has stopped flowing the FSD has operated satisfactorily.

NOTE: You may hear the FSD valve close within the 3 minute period but always check that the gas has stopped flowing.

Fig. 9

3.0 - 5.0mm

12

Page 12
Image 12
Athena Technologies A88028 manual Test for Spillage, Check Ignition, Check Operation of FSD