Ativa 516-015 Troubleshooting, Limited Two Year Product Warranty, Replace Battery Cartridge, Help

Models: 516-015

1 2
Download 2 pages 41.16 Kb
Page 2
Image 2
TROUBLESHOOTING

TROUBLESHOOTING

SPECIFICATIONS

 

 

SPECIFICATIONS LIMITED TWO YEAR PRODUCT WARRANTY LIMITED TWO YEAR PRODUCT WARRANTY

Problem

Possible Cause

Corrective Action

 

 

 

UPS will not switch on.

UPS not connected to AC power source.

Ensure the UPS is securely connected to an AC outlet.

 

 

 

 

UPS circuit breaker “tripped”.

Disconnect non-essential equipment from the UPS. Reset (push in)

 

 

the rear panel circuit breaker. Switch on the UPS and plug in devices

 

 

one at a time. If the circuit breaker trips again, disconnect the device

 

 

that caused the breaker to trip.

 

 

 

 

Internal battery is not connected.

Connect battery cartridge (see Connect Battery Cartridge).

 

 

 

 

Utility input voltage quality is out of range.

Consider adjusting the transfer voltage and sensitivity. See Transfer

 

 

Voltage and Sensitivity Adjustment.

 

 

 

UPS does not power essential

Equipment was plugged into a Surge Only outlet.

Unplug device from 'Surge Only' outlet and move to a 'Battery

equipment during an outage.

 

Backup' outlet.

 

 

 

UPS operates on battery although

The UPS's plug has partially pulled out of the wall

Verify the UPS's plug is fully inserted into the wall, and that power

utility power exists.

outlet, wall outlet has been turned off, or its circuit

is present at the wall outlet.

 

breaker has tripped.

 

 

 

 

 

Unit is in the midst of performing an automatic self

No action is necessary.

 

test.

 

 

 

 

 

Utility input voltage is out of range, frequency is out

Consider adjusting the transfer voltage and sensitivity. See Transfer

 

of range or the wave form is distorted.

Voltage and Sensitivity Adjustment.

 

 

 

UPS does not provide expected

UPS is heavily loaded.

Unplug non-essential equipment (printers, scanners, etc.) from the

backup time.

 

Battery Backup outlets and plug into 'Surge Only' outlets.

 

 

 

 

UPS battery cartridge is discharged due to recent

Charge the battery cartridge for 24 hours. UPS runtime is reduced

 

power outage and has not had time to recharge.

until the battery cartridge is fully charged.

 

 

 

 

Battery has reached the end of its life.

Replace battery cartridge (see Order Replacement Battery

 

 

Cartridge).

 

 

 

Red Replace Battery indicator is on.

Battery has reached the end of its life.

Refer to Replace Battery Cartridge, and replace the battery cartridge.

 

 

 

Red Overload indicator is on or

Connected equipment is drawing more power than

Move one or more equipment power plugs from Battery Backup

flashing.

the UPS can provide.

outlets to Surge Only outlets.

 

 

 

Blue On Line indicator is on and all

Internal UPS fault.

Contact Ativa Technical Support (see Ativa Contact Information).

other front panel indicators are

 

 

flashing.

 

 

 

 

 

REPLACE BATTERY CARTRIDGE

1Problem

2Possible CauseCorrective Action

Item

1200 VA

 

 

On-line Input Voltage Range

88 - 139 VAC

(default settings)

 

 

 

Automatic Voltage Regulation (AVR)

+12% (Boost Only)

 

 

On-line Frequency Range

57 - 63 Hz (Autosensing)

 

 

On-battery Waveshape

Stepped Sine Wave

 

 

Maximum Load

720 W

 

 

Typical Recharge Time

24 Hours

 

 

Operating Temperature

32o to 104oF

 

0o to 40oC

Storage Temperature

23o to 113oF

 

-5oto 45oC

Operating / Storage Relative Humidity

0 to 95% non-condensing

Size (H x W x D)

8.7 inch X 5.1 inch X 13.8 inch

 

220 mm X 130 mm X 350 mm

Weight

29.7 lbs (13.5 kg)

Shipping Weight

33.2 lbs (15.1 kg)

EMI Classification

FCC / DOC Class B Certified

Approvals

TUV C-US certified per UL 1778, CSA 22.2

 

No. 107.1, and NOM-001

Notice: This device complies with part 68 and part 15 of the FCC rules. Operation is

subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for Class B digital devices, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on. The user is encouraged to try to correct the interference by one or more of the following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and the receiver.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

On the bottom of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.

Modifications not approved by the party responsible for compliance could void user’s authority to operate the equipment.

The limited warranty covers the original purchase of a new product used for normal commercial, personal or household use. Office Depot, Inc. (ODP) warrants its products will be free from defects in materials and workmanship (normal wear and tear excepted) for two

(2)years from the date of purchase, except as provided below. ODP, at its option, will replace with a comparable product, free of charge, any product which fails under normal use as a result of such defect. This warranty does not apply to damage caused by fire, accident, negligence, misuse, improper cleaning or other circumstances not directly attributable to manufacturing defects.

ODP PROVIDES THIS LIMITED WARRANTY IN LIEU OF ALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED. EXPRESSLY EXCLUDED ARE ALL WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY. ODP’S SOLE OBLIGATION AND THE USER’S EXCLUSIVE REMEDY UNDER THIS WARRANTY SHALL BE LIMITED TO THE REPAIR OR REPLACEMENT AT ODP’S SOLE DESCRETION AND COST, OF PRODUCT OR COMPONENTS.

IN NO EVENT SHALL ODP, ITS AFFILIATES, SUBSIDIARIES, SUPPLIERS OR PARENT COMPANIES BE RESPONSIBLE FOR CONSEQUENTIAL, SPECIAL, OR INCIDENTIAL DAMAGES ARISING OUT OF A CLAIM OF DEFECTIVE PRODUCT EVEN IF ODP HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.

SOME STATES OR PROVINCES DO NOT ALLOW THE EXCLUSION OF IMPLIED WARRANTIES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS OR THE EXCLUSION OR LIMITATION OF INCIDENTIAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY STATE OR PROVINCE.

THIS WARRANTY APPLIES ONLY TO THE U.S. AND CANADA.

ATIVA CONTACT INFORMATION

For Technical Support and Returns, please call:

1-877-777-HELP (1-877-777-4357)

990-2491

Page 2
Image 2
Ativa 516-015 Troubleshooting, Limited Two Year Product Warranty, Replace Battery Cartridge, Ativa Contact Information