Owner’s Manual

ECM-RACEWY

ECM-20, ECM-20M, & ECM-30

 

 

 

ECM-20/ECM-20M Module System Wiring Configuration

Example 1 - Single 20A AC Line

ECM wiring configuration showing one 20A AC main line coming into an ECM-20M then paralleling with five ECM-20 type modules. Note: It appears that the wiring is in series but the ECM Module In/Out terminals are in parallel on the PCB.

AC main

in 20A

Example 2 - Dual 20A AC Line (40A)

ECM wiring configuration showing two 20A AC main line coming into the raceway for a total of 40A available. The 20A legs are separated by feeding a 20A leg to two different ECM-20M Modules. The leg is then paralleled with two ECM-20 type modules. Note: It appears that the wiring is in series but the ECM Module In/Out terminals are in parallel on the PCB.

AC main

in 20A #1

AC main

in 20A #2

ECM Module Connection to an ECS-6RM Controller

ECS-6RM Control Ports for the ECM Modules

Up to six AC Main circuits can be activated or monitored by the ECS-6RM. Each ECM control port connects to one of the following ECM modules: ECM-20, ECM-20M, ECM-30, ECM-15SH and ECM-20SH. For connection between the ECS-6RM and an ECM module use a 5 conductor cable that is a minimum of 22 gauge wire. We suggest using CAT5 cable due to the common availability. Pay special attention to the port connections and DO NOT MISS WIRE or damage may occur. The distance between the ECS-6RM and an ECM module can be up to 1000ft.

(+)= 5VDC, G = Circuit Ground, V = AC Voltage Status Signal, A = AC Current Status Signal, D = Fault Status Signal, all signals are of low voltage and current.

Single ECM-20 Control Port