ECM Troubleshooting

ECM-RACEWY

Owner’s Manual

ECM-20, ECM-20M, & ECM-30

 

 

 

ECM Troubleshooting

Note: ALL TROUBLESHOOTING SHOULD BE DONE BY A CERTIFIED ELECTRICIAN

Issue 1 - Incoming AC LED is not illuminated.

Possible Cause 1

Incoming AC Mains circuit breaker has tripped due to excessive load.

Action Needed

Check the AC outlet that the ECM is plugged into for 120V AC voltage. If no voltage is present, check to see if the AC outlet is on a GFI that has been tripped. If it has not been tripped, trace the AC Mains outlet back to the electrical panel and check the AC Mains breaker to see if it is tripped.

Possible Cause 2

If the AC Mains is correct (120V), internal 15A (ECM-15SH) and 20A (ECM-20, ECM-20m, ECM-20SH) Slow Blow fuse is blown.

Action Needed

Open ECM unit and replace the fuse with a Slow Blow type.

Issue 2 - AC Fault LED is illuminated.

Possible Cause

Although the Clamping Suppression circuit virtually assures protection from most transient voltage spikes and surges, nature has a way of occasionally creating electrical forces that are beyond the capabilities of any device to absorb without some degree of damage. In the rare instance that this occurs, the clamping circuit can be damaged during the suppression.

Action Needed

The unit will need to be repaired or replaced. It is important to have all equipment that was connected to that AC Mains Line to be inspected for proper operation.

Issue 3 - ECM Active LED is not illuminated.

Possible Cause

Manual slide switch is not set to On.

Issue 4 - Unit is set to External Trigger, the Incoming AC LED is illuminated but the Active LED is not illuminated.

Possible Cause 1

External Switch is not connected across the “D” and “+” terminals.

Possible Cause 2

External DCV is not connected across the “+” and “G” terminals.

Possible Cause 3

External DCV voltage polarity is not correct across the “+” and “G” terminals.

Possible Cause 4

External DCV voltage is too low to activate the trigger circuit. Must be a minimum of 5vDC.