Atlas Sound specifications AP-15U, AP-15TU, AP-15TUC INSTALLATION INSTRUCTIONS, Specifications

Models: AP-15U

1 1
Download 1 pages 58.52 Kb
Page 1
Image 1
AP-15U, AP-15TU, AP-15TUC INSTALLATION INSTRUCTIONS

AP-15U, AP-15TU, AP-15TUC INSTALLATION INSTRUCTIONS

GENERAL DESCRIPTION

Atlas Sound Models AP-15U, AP-15TU and AP-15TUC are high efficiency, U.L. Listed double re-entrant type loudspeakers. They comply with the requirements of UL Standard 1480, Fire Protective Signalling Speakers.

They are designed to be used in conjunction with compatible control equipment for high intelligibility reproduction of audible emergency and protective signals as well as voice messages.

Model AP-15TUC includes a supervisory capacitor and is suitable for installation in systems employing supervised circuitry (25V/70.7V). Maximum supervised circuit voltage is 24 VDC.

For use in ambient temperature ranges from -40˚C to 66˚C.

 

 

SPECIFICATIONS

 

L

 

D

 

 

 

 

 

 

 

SSIFI

 

 

 

 

 

C

A

E

 

 

 

 

 

 

UR

L

POWER:

15 Watts RMS

 

FREQUENCY RESPONSE:

400-4,000Hz

 

 

SOUND LEVEL:

103dB UL 10' Rating

(AP-15U Only)

CONDUIT CONNECTION:

For 12" Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Tap Selector Switch

Switch

Impedance

25V

*db@

70V

*db@

 

 

Position

 

Line

10 Ft.

Line

10 Ft.

 

 

1

5.0 K

-

 

.9 W

93

 

 

 

 

 

2

2.5 K

-

 

1.8 W

96

 

 

3

1.3 K

.48 W

90

3.8 W

98

2"

 

 

 

 

4

666

.94 W

93

7.5 W

101

 

 

5

333

1.8 W

96

15.0 W

103

 

 

6

89

7.5 W

101

Do Not Use

 

 

7

45

15.0 W

103

On 70 V.

 

 

* UL 3dB Increment Rating

1 3/4"

GENERAL DESCRIPTIONSPECIFICATIONS 2 7/8" DIA

1/2" BANDING SLOT

9/32" DIA 3 HOLES

120 DEG. APART,

ON 2.312 DIA B/C

NOTE: Terminal #2 is the positive terminal

Mounting Dimensions

 

 

WIRING DIAGRAM

To conform with UL requirements, wires must be connected as shown in wiring diagram.

NOTE: The maximum wire size that can be connected to this device is 18 Gauge!

From

Speaker 1

Speaker 2

Amplifier

 

 

To next Speaker or End of Line Resistor

CAUTION: Do Not loop wires under screw terminals. Break wire run to provide supervision of connection. Installation must comply with all Building Codes and NFPA guidelines. Installation must adhere to N.E.C. and NFPA 70/72 wiring directives and comply with all National and Local Building Codes.

Specifications are subject to change without notice

www.AtlasSound.com

1601 JACK MCKAY BOULEVARD ENNIS, TEXAS U.S.A. •

TELEPHONE: (800) 876-3332

FAX: (800) 765-3435

© 2005 ATLAS SOUND LP

Printed in U.S.A.

00105

ATS000739 RevD 01/056

PN 386854

Page 1
Image 1
Atlas Sound specifications AP-15U, AP-15TU, AP-15TUC INSTALLATION INSTRUCTIONS, General Description, Specifications