Aube Technologies TH146-N-DE Configuration Menu, Parameters Display Options Default Description

Models: TH146-N-DE

1 8
Download 8 pages 49.15 Kb
Page 4
Image 4

Configuration Menu

Item

Parameters

Display

Options

Default

Description

 

 

 

 

 

 

1

Temperature scale

 

°C / °F

°C

Select the temperature display format.

 

 

 

 

 

 

2

Balance point low

 

-30°C to 10°C

-10°C

Set the bP L value (see section 4.2).

 

(-22°F to 50°F)

(14°F)

 

 

 

 

 

 

 

 

 

 

3

Balance point high

 

-5°C to 30°C

5°C

Set the bP H value (see section 4.2).

 

(23°F to 86°F)

(41°F)

 

 

 

 

 

 

 

 

 

 

4

Defrost point

 

-10°C to 15°C

10°C

During defrost, auxiliary heating is activated when the outside

 

(14°F to 59°F)

(50°F)

temperature is below the defrost point (see section 4.3).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set according to the type of heat pump installation (see section

 

 

 

 

 

4.4).

 

 

 

 

 

Ad (add-on): Use this setting when the indoor coils are located

5

Installation type

 

Ad / nr

Ad

downstream of the auxiliary heat source. This is generally the

 

case for add-on installations.

 

 

 

 

 

 

 

 

 

 

nr (normal): Select this setting when the indoor coils are located

 

 

 

 

 

upstream of the auxiliary heat source. This is generally the case

 

 

 

 

 

for new installations.

 

 

 

 

 

 

6

Cycles per hour

 

2 to 6

4

Allows you to select the number of cycles per hour. It is recom-

 

mended to use the default setting except in exceptional cases.

 

 

 

 

 

 

 

 

 

 

 

7

“Smart fan”

 

On / OF

OF

On: “smart fan” is On (see section 4.5).

 

OF: “smart fan” is Off.

 

 

 

 

 

 

 

 

 

 

 

8

Interstage delay

 

5 to 90 min.

10 min.

Set the interstage delay (see section 4.6).

 

 

 

 

 

 

 

 

 

 

 

Select between displaying the outdoor temperature or display-

 

 

 

 

 

ing the indoor humidity level.

9

Outdoor

 

On / OF

On

On: Displays the outdoor temperature.

temperature display

 

OF (Off): Displays the indoor humidity level.

 

 

 

 

 

 

 

 

 

NOTE: To display the outdoor temperature, the outdoor sensor

 

 

 

 

 

must be connected.

 

 

 

 

 

 

 

 

 

 

 

HE (Heat): The humidifier can operate only when heating is

 

Humidifier

 

 

 

activated.

10

 

HE / Fn

HE

Fn (Fan): The humidifier can operate as long as the fan is run-

operating mode

 

 

 

 

 

ning.

 

 

 

 

 

 

 

 

 

 

NOTE: The humidifier is disabled when cooling is activated.

 

 

 

 

 

 

 

 

 

 

 

Allows you to place the humidity adjustment to automatic mode.

 

 

 

 

 

On (automatic): The humidity level is automatically regulated by

11

Automatic humidity

 

On / OF

OF

the controller according to the outdoor temperature to avoid

adjustment

 

condensation or ice formation on windows (see item 12).

 

 

 

 

 

 

 

 

 

OF (manual): The user manually sets the humidity level (see

 

 

 

 

 

item 12).

 

 

 

 

 

 

 

 

 

 

 

Set the desired humidity level. This parameter is available only

 

Humidity setpoint

 

5% to 60%

5%

when the humidity control is placed in manual mode (see item

 

 

 

 

 

11).

 

 

 

 

 

 

12

 

 

 

 

Allows the user to apply an offset to the automatic humidity con-

 

 

 

 

trol. For example, the user can enter a negative offset if there is

 

 

 

 

 

 

Humidity offset

 

-9% to 9%

0%

still ice formation or condensation on the windows. This param-

 

 

 

 

 

eter is available only when the humidity control is placed in

 

 

 

 

 

automatic mode (see item 11).

 

 

 

 

 

 

NOTE: Only the humidity setpoint or humidity offset (item 12) is available when the controller is placed in user mode (SW2 switch).

TH146-N-DE

400-280-000-G

9/22/06

4/8

Page 4
Image 4
Aube Technologies TH146-N-DE manual Configuration Menu, Parameters Display Options Default Description