TH146-P-DE

Installation Guide

Programmable Heat Pump Controller

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC144-03 Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH146-P User Console

 

 

 

 

 

 

 

 

 

 

 

CT280-HP-2H1C Control Module

Temperature Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Introduction

1.1 Applications

The TH146-P-DE programmable controller can be used to control a heat pump system. The following devices can be connected to the controller:

heat pump

auxiliary heating (furnace) air recirculation fan humidifier

dual-register meter (dual energy)

remote control device (for the unoccupied mode)

1.2 Supplied Parts

CT280-HP-2H1C control module

TH146-P console with two wall anchors and mounting screws

AC144-03 outdoor temperature sensor (3 m or 10 ft) with mounting clip (see section 2.7)

1.3 Accessories

RC845 relay (see section 2.5)

AC146-410 plenum temperature sensor (see section 2.8)

CT241 telephone controller (see section 2.10)

2. Installation

2.1 Control Module (CT280-HP-2H1C)

Install the control module on the furnace’s electrical panel, away from the heat source.

2.2 User Console (TH146-P)

Install the console in the area where you wish to measure the tem- perature and humidity. Avoid locations where there are air drafts (e.g., top of staircase or air outlet) or stagnant air (behind a door). Do not install the console on a wall hiding air ducts nor expose it to direct sunlight.

NOTE: If this controller replaces an existing thermostat, the wires that were connected to the thermostat can be used to connect the console. The maximum wire length is 30 m (100 feet).

1)Choose a location about 5 ft. (1.5 m) above the floor on an inside wall.

2)Loosen the captive screw under the console.

3)Detach the console from its base by pulling the bottom section.

4)Secure the base using the wall anchors and screws.

5)Connect the console to controller terminals TH and TH (no polarity).

2.3 Heat Pump

Connect the heat pump to the controller as follows:

Controller terminals R and C to heat pump terminals R and C (see section 2.4)

Controller terminal Y to heat pump terminal Y

Controller terminal O/B to heat pump terminal O

Controller terminal WW to heat pump terminal WW

TH146-P-DE

400-280-004-C

11/29/06

1/9

Page 1
Image 1
Aube Technologies TH146-P-DE manual Introduction, Installation Guide