Configuration Menu
Item | Parameters | Display | Options | Default | Description |
|
|
|
|
|
|
1 | Time format |
| 12 Hr / 24 Hr | 24 Hr | Select the time display format. |
|
|
|
|
|
|
|
|
|
|
| On: Heating or cooling starts in advance (as determined by the |
|
|
|
|
| controller) so that the desired temperature is attained at the set |
|
|
|
|
| times. |
2 | Early Start |
| On / OF | OF | OF (Off): Heating or cooling starts at the set times. |
| NOTE: Early Start applies for periods 1 and 3 (P1 and P3) only. | ||||
|
|
|
|
| |
|
|
|
|
| When this feature is enabled, heating or cooling will start in |
|
|
|
|
| advance of the set time for P1 and P3 but will start at the set |
|
|
|
|
| time (not earlier) for P2 and P4. |
|
|
|
|
|
|
|
|
|
|
| OF (Off): The normal time is used all year long. |
|
|
|
|
| 1 : The controller switches to daylight savings time on the first |
| Automatic daylight |
|
|
| Sunday of April and to normal time on the last Sunday of Octo- |
3 |
| OF / 1 / 2 | OF | ber. | |
savings adjustment |
| ||||
|
|
|
| 2 : The controller switches to daylight savings time on the second | |
|
|
|
|
| |
|
|
|
|
| Sunday of March and to normal time on the first Sunday of |
|
|
|
|
| November. |
|
|
|
|
|
|
4 | Temperature scale |
| °C / °F | °C | Select the temperature display format. |
|
|
|
|
|
|
5 | Balance point low |
| Set the bP L value (see section 4.2). | ||
| (14°F) | ||||
|
|
|
| ||
|
|
|
|
|
|
6 | Balance point high |
| 5°C | Set the bP H value (see section 4.2). | |
| (23°F to 86°F) | (41°F) | |||
|
|
|
| ||
|
|
|
|
|
|
7 | Defrost point |
| 10°C | During defrost, auxiliary heating is activated when the outside | |
| (14°F to 59°F) | (50°F) | temperature is below the defrost point (see section 4.3). | ||
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Set according to the type of heat pump installation (see section |
|
|
|
|
| 4.4). |
|
|
|
|
| Ad |
8 | Installation type |
| Ad / nr | Ad | downstream of the auxiliary heat source. This is generally the |
| case for | ||||
|
|
|
|
| |
|
|
|
|
| nr (normal): Select this setting when the indoor coils are located |
|
|
|
|
| upstream of the auxiliary heat source. This is generally the case |
|
|
|
|
| for new installations. |
|
|
|
|
|
|
9 | Cycles per hour |
| 2 to 6 | 4 | Allows you to select the number of cycles per hour. It is recom- |
| mended to use the default setting except in exceptional cases. | ||||
|
|
|
|
| |
|
|
|
|
|
|
10 | “Smart fan” |
| On / OF | OF | On: “Smart fan” is On (see section 4.5). |
| OF: “Smart fan” is Off. | ||||
|
|
|
|
| |
|
|
|
|
|
|
11 | Interstage delay |
| 5 to 90 min. | 10 min. | Set the interstage delay (see section 4.6). |
|
|
|
|
|
|
|
|
|
|
| HE (heat): The humidifier can operate only when heating is acti- |
| Humidifier |
|
|
| vated. |
12 |
| HE / Fn | HE | Fn (fan): The humidifier can operate as long as the fan is run- | |
operating mode |
| ||||
|
|
|
| ning, whether heating is activated or not. | |
|
|
|
|
| |
|
|
|
|
| NOTE: The humidifier is disabled when cooling is activated. |
|
|
|
|
|
|
NOTE: Only items 1 to 4 are available when the controller is placed in user mode (SW2 switch).
11/29/06 | 4/9 |