Schneider Electric 61 user manual Fault parameters, Code, Description, Internal - hard init

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 103
Image 103
37: [Internal - hard init.]

Fault parameters

Code

 

 

Description

 

 

 

 

((LFT),

35:

 

Reserved

continued)

36:

 

Reserved

 

37: [Internal - hard init.]

(InF7)

Initialization of the drive is incomplete

 

38: [External fault com.]

(EPF2)

Fault triggered by a communication network

 

39: [Application fault]

(APF)

"Controller Inside" card fault

 

40: [Internal-ctrl supply]

(InF8)

The control supply is not correct

 

41:

 

Reserved

 

42: [PowerSuite com.]

(SLF2)

Fault communicating with PowerSuite

 

43:

 

Reserved

 

44: [Torque/current lim]

(SSF)

Switch to torque limitation

 

45: [HMI com.]

(SLF3)

Fault communicating with the graphic display terminal

 

46: [Power removal]

(PrF)

Fault with the drive’s "Power removal" safety function

 

47: [PTC2 probe]

(PtF2)

PTC2 probes open or short-circuited

 

48: [PTC2 overheat]

(OtF2)

Overheating of the PTC2 probes detected

 

49: [LI6=PTC probe]

(PtFL)

PTC probes on input LI6 open or short-circuited

 

50: [LI6=PTC overheat]

(OtFL)

Overheating of PTC probes detected on input LI6

 

51: [Internal- I measure]

(InF9)

The current measurements are not correct

 

52: [Internal-mains circuit](InFA)

The input stage is not operating correctly

 

53: [Internal-th. sensor]

(InFb)

The drive temperature sensor is not operating correctly

 

54: [IGBT overheat]

(tJF)

Drive overheated

 

55: [IGBT short circuit]

(SCF4)

Power component fault

 

56: [Motor short circuit]

(SCF5)

Short-circuit at the drive output

 

57:

 

Reserved

58:[Out. contact. stuck] (FCF1) The output contactor remains closed although the opening conditions have been met

59:[Out. contact. open] (FCF2) The output contactor remains open although the closing conditions have been met

60: [Internal-time meas.]

(InFC)

Fault on the electronic time measurement component

61: [AI2 input]

(AI2F)

Non-conforming signal on analog input AI2

62: [Encoder]

(EnF)

Encoder feedback fault

63:[Thyr. soft charge] (CrF2) DC bus charging fault (thyristors)

64: [input contactor]

(LCF)

The drive is not turned on even though [Mains V. time out] (LCt) has elapsed

65: [DB unit sh. circuit]

(bUF)

Short-circuit output from braking unit

66:

 

Reserved

67: [IGBT desaturation]

(HdF)

Short-circuit or grounding at the drive output

68: [Internal-option]

(InF6)

The option installed in the drive is not recognized

69: [Internal- CPU]

(InFE)

Internal microprocessor fault

70: [DBR overload]

(bOF)

The braking resistor is under excessive stress

71:[AI3 4-20mA loss] (LFF3) Loss of the 4-20 mA reference on analog input AI3

72:[AI4 4-20mA loss] (LFF4) Loss of the 4-20 mA reference on analog input AI4

73: [Cards pairing]

(HCF)

The [CARDS PAIRING] (PPI-)function has been configured and a drive card has

 

 

been changed

74: [No Flow Flt]

(nFF)

No fluid

75: [Power Ident]

(PtrF)

Inconsistency between control card and power card

76 to 99:

 

Reserved

100: [Proc. Underload Flt]

(ULF)

Process underload

101: [Proc. Overload Flt]

(OLC)

Process overload

102: [PI Feedback]

(SPIF)

PID feedback below lower limit

103

Page 103
Image 103
Schneider Electric 61 user manual Fault parameters, Code, Description, Internal - hard init