Schneider Electric 61 user manual Status parameters, Code, Possible values in CiA402 profile

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 80
Image 80
Possible values in CiA402 profile

Status parameters

Code

Description

Possible values in CiA402 profile

bit 0: "Ready to switch on", awaiting power section line supply

bit 1: "Switched on", ready

bit 2: "Operation enabled", running

bit 3: "Fault"

=0: No fault

=1: Fault

bit 4: "Voltage enabled", power section line supply present

=0: Power section line supply absent

=1: Power section line supply present

When the drive is powered by the power section only, this bit is always at 1. bit 5: "Quick stop"/Emergency stop

bit 6: "Switched on disabled", power section line supply locked

bit 7: "Warning", alarm

=0: No alarm

=1: Alarm

bit 8: Reserved

bit 9: "Remote", command or reference via the network

=0: Command or reference via the terminals

=1: Command or reference via the network

bit 10: "Target reached", reference reached

=0: The reference is not reached

=1: The reference has been reached

When the drive is in speed mode, this is the speed reference. When the torque function is activated, refer to the description of this function (see the Programming Manual). When the drive stops, the reference has been reached.

bit 11: "Internal limit active", reference outside limits

=0: The reference is within the limits

=1: The reference is not within the limits

When the drive is in speed mode, the limits are defined by the "Low speed (LSP)" and "High speed (HSP)" parameters. When the torque function is activated, refer to the description of this function (see the Programming Manual).

bit 12: Reserved

bit 13: Reserved

bit 14: "Stop key", STOP via stop key

=0: STOP key not pressed

=1: Stop triggered by the STOP key on the graphic display terminal bit 15:"Direction", direction of rotation

=0: Forward rotation at output

=1: Reverse rotation at output

The combination of bits 0, 1, 2, 4, 5 and 6 defines the state in the DSP 402 state chart (see the CiA402 profile section).