I/O profile

Definition

The behavior of the drive is identical whether via the network or via the terminals.

The I/O profile is achieved via the following configuration:

Menu

Parameter

Value

 

 

 

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

 

 

As well as to logic inputs of the terminals, drive functions can be assigned to control word bits.

A function input can be assigned to:

A terminal input (LI2 to LI14)

A Modbus control word bit (C101 to C115)

A CANopen control word bit (C201 to C215)

A network card control word bit (C301 to C315)

A Controller Inside control word bit (C401 to C415)

A switched bit (Cd00 to Cd15): See "Command/reference switching" section.

Schematic diagrams:

Fixed assignment on CANopen:

CANopen control word

bit 15

bit 14

bit 13

bit 12

bit 11

bit 10

bit 9

bit 8

bit 7

bit 6

bit 5

bit 4

bit 3

bit 2

bit 1

bit 0

Function

C201

A

C202

B

Fixed assignment to terminals and on CANopen:

CANopen control word

bit 15

bit 14

bit 13

bit 12

 

bit 11

bit 10

bit 9

bit 8

 

bit 7

bit 6

bit 5

bit 4

 

bit 3

bit 2

bit 1

bit 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals

 

 

 

 

 

 

LI14

LI13

LI12

LI11

LI10

LI9

LI8

LI7

LI6

LI5

LI4

LI3

LI2

LI1

C201

C202

LI2

Function

A

B

C

13

Page 13
Image 13