Schneider Electric 61 Quick stop active, Fault reaction active, Summary, CiA402 profile

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 21
Image 21
6 - Quick stop active

CiA402 profile

6 - Quick stop active

Emergency stop

The drive performs a fast stop, after which restarting will only be possible once the drive has changed to the "Switch on disabled" state. During fast stop, the drive is unlocked and power is supplied to the motor.

The configuration parameters cannot be modified.

The condition for transition 12 to the state "2 - Switch on disabled" depends on the value of the parameter "Quick stop option code" (QSTD):

If the "Quick stop option code" parameter has the value 2, the drive stops according to the fast stop ramp and then goes into the state "2 - Switch on disabled".

If the "Quick stop option code" parameter has the value 6, the drive stops according to the fast stop ramp and then remains in the state "6 - Quick stop active" until:

-A "Disable voltage" command is received

-Or the STOP key is pressed

-Or there is a freewheel stop command via the terminals

7 - Fault reaction active

Transient state during which the drive performs an action appropriate to the type of fault.

The drive function is activated or deactivated according to the type of reaction configured in the fault management parameters.

8 - Fault

Drive faulty.

The drive is locked, no power is supplied to the motor.

Summary

State

Power section line supply for

Power supplied to motor

Modification of configuration

separate control section

parameters

 

 

 

 

 

 

1 - Not ready to switch on

Not required

No

Yes

 

 

 

 

2 - Switch on disabled

Not required

No

Yes

 

 

 

 

3 - Ready to switch on

Not required

No

Yes

 

 

 

 

4 - Switched on

Required

No

Yes, return to "2 - Switch on

disabled" state

 

 

 

 

 

 

 

 

 

Yes, apart from an open-loop

 

5 - Operation enabled

Required

drive with a zero reference or in

No

the event of a "Halt" command

 

 

 

 

 

for an open-loop drive.

 

 

 

 

 

6 - Quick stop active

Required

Yes, during fast stop

No

 

 

 

 

7 - Fault reaction active

Depends on fault management

Depends on fault management

-

configuration

configuration

 

 

 

 

 

 

8 - Fault

Not required

No

Yes

 

 

 

 

21

Page 21
Image 21
Schneider Electric 61 Quick stop active, Fault reaction active, Summary, CiA402 profile, Switch on disabled, Switched on