Priority stops

Priority stops on the graphic display terminal

If the graphic display terminal is not the active command channel, pressing the STOP key on the graphic display terminal causes a freewheel stop if:

• The [Stop Key priority] (PSt) parameter in the [1.6 - COMMAND] (CtL-)menu is configured to [Yes] (YES) (factory setting).

If the graphic display terminal is the active command channel, the STOP key causes a stop according to the type of stop configured in the [Type of stop] (Stt) parameter, regardless of the value of the [Stop Key priority] (PSt) parameter.

The effect of the graphic display terminal does not depend on the profile.

Priority stops via the terminals or the network

I/O profile

In the I/O profile:

Stop and fault commands, configured as fixed assignments (LIpp, C1pp, C2pp, C3pp, C4pp), on terminal inputs or control word bits, have priority even if the channel is not active.

Commands, configured as switched assignments (Cd00 ... Cd15), are active if and only if the channel is active.

Fixed assignments are configured by the following values:

Channel

 

 

Run on state command

 

Run on edge command

 

 

 

[2 wire] (2C)

 

 

[3 wire] (3C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive terminals

 

 

 

LI2 ... LI6

 

 

LI3 ... LI6

 

 

 

 

 

 

 

 

 

Logic I/O card

 

 

 

 

LI7 ... LI10

 

 

 

 

 

 

 

 

 

 

Extended I/O card

 

 

 

 

LI11 ... LI14

 

 

 

 

 

 

 

 

 

 

 

Integrated Modbus

 

 

 

C101 ... C115

 

 

C102 ... C115

 

 

 

 

 

 

 

 

 

CANopen

 

 

 

C201 ... C215

 

 

C202 ... C215

 

 

 

 

 

 

 

 

 

Communication card

 

 

 

C301 ... C315

 

 

C302 ... C315

 

 

 

 

 

 

 

 

 

"Controller Inside" card

 

 

 

C401 ... C415

 

 

C402 ... C415

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

Configuration

 

= 0

= 1

 

Value for starting(1)

Freewheel stop

[Freewheel stop ass.] (nSt)

 

Stop

 

No stop

 

1

 

 

 

 

 

 

 

 

Fast stop

[Fast stop assign.] (FSt)

 

Stop

 

No stop

 

1

 

 

 

 

 

 

 

 

DC injection braking

[DC injection assign.] (dCI)

 

No braking

 

Braking

 

0

 

 

 

 

 

 

 

 

External fault

[External fault ass.] (EtF)

 

No fault

 

Fault

 

0

 

 

 

 

 

 

 

 

 

(1)If the assignment is fixed, the value necessary for starting, even if another channel is active.

In run on edge command, configured by [3 wire] (3C):

The stop command (run enable) is assigned by construction to switched order 0 (equivalent to Cd00):

It is active at the terminals (LI1) only if the terminals are active

It is active via the network (bit 0) only if the network is active

49

Page 49
Image 49
Schneider Electric 61 Priority stops on the graphic display terminal, Priority stops via the terminals or the network