Reference parameters

Reference parameters

References (speed)

Code

 

Description

 

 

 

 

 

FrHd

Parameter name:

Speed reference before ramp

 

 

 

 

 

 

 

Logic address:

8605 = 16#219D

Type:

INT

 

CANopen index:

2038/6

Read/write:

R

 

INTERBUS index:

6043/0

Unit:

rpm

 

DeviceNet path:

8C/01/06

 

 

 

 

 

 

 

FrOd

Parameter name:

Speed reference after ramp

 

 

 

Terminal display:

 

 

 

 

CiA402 name:

vl velocity demand

 

 

 

DRIVECOM name:

Speed-Reference-Variable

 

 

 

 

 

 

 

 

Logic address:

8641 = 16#21C1

Type:

INT

 

CANopen index:

6043/0

Read/write:

R

 

INTERBUS index:

5FB9/DB

Unit:

rpm

 

DeviceNet path:

8C/01/2A

 

 

 

 

 

 

 

 

Parameter conforming to CiA402 profile

 

 

 

Signed value.

 

 

 

 

This parameter is linked to the "Frequency after ramp" (FRO) parameter for which the unit is 0.1 Hz.

 

 

 

 

FrH

Parameter name:

Frequency reference before ramp

 

 

Terminal display:

[Frequency ref.]

 

 

 

 

 

 

 

 

Logic address:

3203 = 16#0C83

Type:

INT

 

CANopen index:

2002/4

Read/write:

R

 

INTERBUS index:

5FB9/05

Unit:

0.1 Hz

 

DeviceNet path:

71/01/04

 

 

 

 

 

 

 

FrO

Parameter name:

Frequency reference after ramp

 

 

 

 

 

 

 

Logic address:

9021 = 16#233D

Type:

INT

 

CANopen index:

203C/16

Read/write:

R

 

INTERBUS index:

5FB9/DC

Unit:

0.1 Hz

 

DeviceNet path:

8E/01/16

 

 

 

 

 

 

 