Configuration saving and switching

To save the parameter, a save command must be executed using bit 1 of the extended control word (CMI).

Display terminal

Current

configuration

(RAM)

Extended control word:

Save (CMI,1)

Modbus

CANopen

Network

Set to 1

Industrial

HMI

terminal

PLC

Configuration 0

(EEPROM)

Configuration 1

(EEPROM)

Configuration 2

(EEPROM)

Factory settings

The save command is only active if the drive is stopped, and not in "5-Operation enabled" state.