At the terminals:

Priority stops

CiA402 profile

In the CiA402 profile, separate or not separate mode:

External stop and fault commands, configured as fixed assignments (LIpp, C1pp, C2pp, C3pp, C4pp), on terminal inputs or control word bits, have priority even if the channel is not active.

Commands, configured as switched assignments (Cd11 ... Cd15), are active if and only if the channel is active.

Fixed assignments are configured by the following values:

Channel

Run on state command

 

Run on edge command

[2 wire] (2C)

 

[3 wire] (3C)

 

 

 

 

 

 

Drive terminals

LI2 ... LI6

 

LI3 ... LI6

 

 

 

 

Logic I/O card

 

LI7 ... LI10

 

 

 

Extended I/O card

 

LI11 ... LI14

 

 

 

Integrated Modbus

 

C111 ... C115

 

 

 

CANopen

 

C211 ... C215

 

 

 

Communication card

 

C311 ... C315

 

 

 

"Controller Inside" card

 

C411 ... C415

 

 

 

 

Cp11 is assigned by default to the reverse direction command [Reverse assign.] (rrS).

At the terminals:

Command

Configuration

= 0

= 1

Value for

State reached from

starting(1)

5-Operation enabled

 

 

 

 

Freewheel stop

[Freewheel stop ass.]

Stop

No stop

1

2-Switch on disabled

(nSt)

 

 

 

 

 

 

 

 

 

 

 

Fast stop

[Fast stop assign.] (FSt)

Stop

No stop

1

4-Switched on

 

 

 

 

 

 

DC injection braking

[DC injection assign.]

No braking

Braking

0

5-Operation enabled

(dCI)

 

 

 

 

 

 

 

 

 

 

 

External fault

[External fault ass.] (EtF)

No fault

Fault

0

8-Fault

 

 

 

 

 

 

(1)If the assignment is fixed, the value necessary for starting, even if another channel is active.

In run on edge command, configured by [3 wire] (3C), the stop command (run enable) is assigned by construction to LI1. This command is active even if the terminals are not the active channel.

Via the network:

Command

Configuration

= 0

= 1

Value for

State reached from

starting(1)

5-Operation enabled

 

 

 

 

Fast stop

[Fast stop assign.] (FSt)

No stop

Stop

0

4-Switched on

 

 

 

 

 

 

DC injection braking

[DC injection assign.]

No braking

Braking

0

5-Operation enabled

(dCI)

 

 

 

 

 

 

 

 

 

 

 

External fault

[External fault ass.] (EtF)

No fault

Fault

0

8-Fault

 

 

 

 

 

 

(1)If the assignment is fixed, the value necessary for starting, even if another channel is active.

In the CiA402 profile, the freewheel stop command [Freewheel stop ass.] (nSt) cannot be assigned to the control word. Freewheel stop is obtained via the "5-Disable operation" or "Halt" command with the Type of Stop [Type of stop] (Stt) parameter configured to [Freewheel] (nSt).

50